Operating instructions

R3G250-AY15-K1

Translation of the original operating instructions

4.5 Connection screen

No.

Conn.

Designation

Function / assignment

PE

PE

Protective earth connection

KL1

1, 2, 3

L1, L2, L3

Supply voltage, voltage range (see type plate), 50/60 Hz

KL2

1

NC

Floating status contact, break with error

KL2

2

COM

Floating status contact, changeover contact, common connection (2 A, max. 250 VAC,
min. 10 mA, AC1)

KL2

3

NO

Floating status contact, close with error

KL3

1

OUT

Analogue output, 0-10 VDC, max. 3 mA, SELV,
Output of the actual motor duty cycle (PWM):
1 V corresponds to 10% PWM,
10 V correspond to 100% PWM.

KL3

2, 8

GND

Signal ground for control interface, SELV

KL3

3, 7

0-10 V

Set value / actual sensor value input 0-10 VDC, impedance 100 kΩ only as alternative to 4-20 mA input, SELV

KL3

4

+10 V

Voltage output 10 VDC (+/-3%), max. 10 mA,
power supply for external devices (e.g. potentiometer), SELV

KL3

5

+20 V

Voltage output 20 VDC (+25%/-10%), max. 50 mA, supply voltage for external devices
(e.g. sensors), SELV

KL3

6

4-20 mA

Set value / actual sensor value input 4-20 mA, impedance 100 Ω, only as alternative to 0-10 V input, SELV

KL3

9, 11

RSB

RS485 interface for MODBUS, RSB

KL3

10, 12

RSA

RS485 interface for MODBUS, RSA

Item no. 53107-5-9970 · ENG · Revision 246486 · Release 2021-11-11 · Page 10 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G250-AY15-K1

Page 1: ...ry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is install...

Page 2: ...Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against acc...

Page 3: ...ng the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vib...

Page 4: ...ith a pressure tap k factor 70 not included in scope of delivery 2 Depth of screw max 16 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 4 Tightening torque 3 5 0 5 Nm Item no 5310...

Page 5: ...ve the unit mm Inlet nozzle 25075 2 4013 with pressure tap not included in scope of delivery Item no 53107 5 9970 ENG Revision 246486 Release 2021 11 11 Page 5 14 ebm papst Mulfingen GmbH Co KG Bachm...

Page 6: ...m papst evaluation loses its validity conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors com...

Page 7: ...with a Ssc value that is greater than or equal to 120 times the rated output of the arrangement 4 CONNECTION AND START UP 4 1 Connecting the mechanical system CAUTION Cutting and crushing hazard when...

Page 8: ...vice protection Nominal voltage Safety fuse Wire cross section Wire cross section UL mm AWG 3 PE AC 200 240 VAC 15 A 1 5 16 3 PE AC 200 240 VAC 20 A 2 5 14 AWG American Wire Gauge 4 2 3 Idle current B...

Page 9: ...trate into the terminal box if water is constantly present at the cable glands To prevent the constant accumulation of water at the cable glands the cable should be routed in a U shaped loop siphon wh...

Page 10: ...0 PWM KL3 2 8 GND Signal ground for control interface SELV KL3 3 7 0 10 V Set value actual sensor value input 0 10 VDC impedance 100 k only as alternative to 4 20 mA input SELV KL3 4 10 V Voltage outp...

Page 11: ...nd off via power supply Switching off the device for maintenance work Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect...

Page 12: ...ient temperature too high Reduce the ambient temperature Let the device cool down To reset the error message switch off the mains supply voltage for a min of 25 s and switch it on again Alternatively...

Page 13: ...ltage to be used corresponds to the peak value of the AC voltage required by the standard What has to be tested How to test Frequency Which measure Check the protective casing against accidental conta...

Page 14: ...ulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets are used in external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite mag...

Reviews: