Operating instructions

K3G900-AS08-01

Translation of the original operating instructions

4.5 Connection diagram

No.

Conn.

Designation

Function/assignment

KL 1

1

L1

Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz

KL 1

2

L2

Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz

KL 1

3

L3

Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz

PE

PE

Ground connection, PE connection

KL 2

1

NO

Status relay, floating status contact, make for failure

KL2

2

COM

Status relay, floating status contact; changeover contact; common connection; contact rating 250 VAC / max.
2 A (AC1) / min. 10 mA

KL2

3

NC

Status relay, floating status contact, break for failure

KL 3

1

RSA

Bus connection RS485, RSA, MODBUS RTU

KL 3

2

RSB

Bus connection RS485, RSB, MODBUS RTU

KL 3

3 / 10

GND

Reference ground for control interface

KL 3

4

Ain1 U

Analog input 1 (set value), 0-10 V, Ri = 100 kΩ, adjustable curves, only usable as alternative to input Ain1I

KL 3

5

+ 10 V

Fixed voltage output 10 VDC, +10 V ±3%; max. 10 mA; short-circuit-proof; power supply for external
devices (e.g. pot)

KL 3

6

Ain1 I

Analog input 1 (set value), 4-20 mA, Ri = 100 Ω, adjustable curves, only usable as alternative to input Ain1U

KL 3

7

Din1

Digital input 1: enable electronics, enable: pin open or applied voltage 5...50 VDC: disable: bridge to GND or
applied voltage < 1 VDC; reset function: triggers software reset after a level change to < 1 V

KL 3

8

Din2

Digital input 2: Switching parameter sets 1/2; according to EEPROM setting, the valid or used parameter set
can be selected via bus or via digital input DIN2. Parameter set 1: pin open or applied voltage 5-50 VDC;
parameter set 2: bridge to GND or applied voltage < 1 VDC

KL 3

9

Din3

Digital input 3: according to EEPROM setting, the integrated controller's direction of action can be selected as
normal/inverse via bus or digital input; normal: pin open or applied voltage 5-50 VDC inverse: bridge to GND
or applied voltage < 1 VDC

KL 3

11

Ain2 U

Analog input 2, measured value 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input Ain2I

KL 3

12

+ 20 V

Fixed voltage output 20 VDC, 20 V +25/-10%, max. 50 mA, short-circuit-proof power supply for external
devices (e.g. sensors)

KL 3

13

Ain2 I

Analog input 2, measured value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input
Ain2U

KL 3

14

Aout

Analog output 0-10 V, max. 5 mA, output of current motor modulation level / of the current motor speed.
Adjustable curve.

Item no. 51810-5-9970 · ENU · Change 99339 · Approved 2018-04-27 · Page 9 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G900-AS08-01

Page 1: ...e permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devi...

Page 2: ...come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries Take appropriate safety measures WARNING Rotatin...

Page 3: ...mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter 3 6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protectiv...

Page 4: ...ion for vibration absorbing elements 3 Cable diameter min 5 mm max 13 mm tightening torque 6 0 9 Nm 4 Cable diameter min 16 mm max 20 5 mm tightening torque 6 0 9 Nm 5 Tightening torque 3 5 0 5 Nm Ite...

Page 5: ...Technical description Weight 220 kg Size 900 mm Motor size 200 Rotor surface Painted black Electronics housing material Die cast aluminum painted black Impeller material Sheet aluminum Inlet nozzle m...

Page 6: ...or that this device is only connected to a connection point with an Ssc value greater than or equal to 250 times the rated output of the arrangement 4 CONNECTION AND STARTUP 4 1 Mechanical connection...

Page 7: ...ss section is at least AWG 26 0 13 mm Protective earth contact resistance according to EN 61800 5 1 Compliance with the resistance specifications according to EN 61800 5 1 for the protective earth con...

Page 8: ...so When connecting ensure that no wire ends fan out Seal the terminal box 4 3 3 Cable routing Water must be prevented from reaching the cable gland along the cable NOTE Damage caused by moisture pene...

Page 9: ...ics enable pin open or applied voltage 5 50 VDC disable bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 V KL 3 8 Din2 Digital input 2 Switching...

Page 10: ...ssively high vibration levels and possibly resonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or...

Page 11: ...matically Device restarts automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Deficient cooling Improve co...

Page 12: ...ce device 6 4 Disposal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst operates an environmental management system which is certified in acc...

Page 13: ...aterials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolyti...

Reviews: