ebm-papst K3G400-RP45-25 Operating Instructions Manual Download Page 7

Operating instructions

K3G400-RP45-25

Translation of the original operating instructions

DANGER
Electrical charge (>50 µC) between phase conductor and
protective earth connection after switching off supply
with multiple devices connected in parallel.

Electric shock, risk of injury
→ Ensure sufficient protection against accidental contact.

Before working on the electrical hookup, short the supply
and PE connections.

CAUTION
Voltage

The fan is a built-in component and has no disconnecting switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole disconnection switch.

→ When working on the fan, secure the system/machine in

which the fan is installed so as to prevent it from being
switched back on.

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.

4.2.1 Requirements

;

Check whether the information on the nameplate matches the
connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

4.2.2 Reactive currents

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and immunity to interference),
reactive currents can be measured in the supply line even
when the motor is at a standstill and the line voltage is switched
on.

The values are typically in the range < 250 mA

At the same time, the effective power in this operating state
(operational readiness) is typically < 4 W.

4.2.3 Residual current circuit breaker (RCCB)

If the use of a residual current device (RCD) is required in your
installation, only AC/DC-sensitive residual current devices
(type B or B+) are permissible. As with variable frequency
drives, residual current devices cannot provide personal safety
while operating the device. When the device power supply is
switched on, pulsed charging currents from the capacitors in the
integrated EMC filter can lead to the instant tripping of residual
current devices. We recommend the use of residual current
circuit breakers (RCCB) with a trip threshold of 300 mA and
delayed tripping (super-resistant, characteristic K).

4.2.4 Locked-rotor protection

Due to the locked-rotor protection, the starting current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Plug connection

4.3.1 Making supply connections

;

Check your connector's pin assignment.

;

Connect the built-in connector with the mating connector.

;

Ensure that the connector is properly engaged.

Item no. 57388-5-9970 · ENU · Change 214130 · Approved 2020-07-14 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G400-RP45-25

Page 1: ...ized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards assoc...

Page 2: ...ntact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and...

Page 3: ...ating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ic...

Page 4: ...ox 2 Connector housing 3 pole GST18 3 Wieland 92 032 9058 1 2 1 N 2 2 PE 2 3 L 3 8 pole connector housing TE 100616 2 4 8 pole connector housing TE 100616 2 Item no 57388 5 9970 ENU Change 214130 Appr...

Page 5: ...tandardized measurement setup 3 4 Technical description Weight 10 06 kg Size 400 mm Motor size 84 Rotor surface Painted black Electronics housing material Die cast aluminum Impeller material PP plasti...

Page 6: ...g hold of the frame Never subject to any impact Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when unpacking device Risk of physical injury such as back injuries Two people shou...

Page 7: ...that the minimum cable cross section is at least AWG 26 0 13 mm 4 2 2 Reactive currents Because of the EMC filter integrated for compliance with EMC limits interference emission and immunity to inter...

Page 8: ...US RSA KL2 KL3 2 RSB RS 485 interface for MODBUS RSB KL2 KL3 3 RSA RS 485 interface for MODBUS RSA KL2 KL3 4 Bridge KL2 KL3 KL2 KL3 5 Bridge KL2 KL3 KL2 KL3 6 RSB RS 485 interface for MODBUS RSB KL2 K...

Page 9: ...n order to obtain a complete picture of the vibrations occurring in the application see Chapter 6 Maintenance malfunctions possible causes and remedies 4 7 Switching off the device Disconnect the devi...

Page 10: ...fe check the fans regularly for proper operation and soiling The frequency of checking is to be adapted accordingly depending on the degree of soiling DANGER Risk of injury from rotating fan Only clea...

Page 11: ...s 6 4 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific legal regulations with regard to the disposal of products or waste o...

Reviews: