background image

Operating instructions

K3G310-BB49-02

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G112-GA

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Type of data definition

ml

Speed (rpm) / min

-1

3140

Power input / W

1650

Current draw / A

2.5

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data in accordance with ecodesign regulation EU 327/
2011

Actual

Request 2015

01 Overall efficiency η

es

/ %

63.1

53.7

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

71.4

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
rating plate on the product.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
County court Stuttgart · HRA 590344
D-74673 Mulfingen

08 Type

K3G310-BB49-02

09 Power input P

ed

/ kW

1.62

09 Air flow q

v

/ m³/h

3780

09 Pressure increase total p

sf

/

Pa

907

10 Speed (rpm) n / min

-1

3145

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data definition with optimum efficiency. The ErP data is determined using a motor-impeller

combination in a standardised measurement configuration.

3.4 Technical features

Mass

22.1 kg

Size

310 mm

Motor size

112

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of impeller

Aluminium sheet

Material of mounting
plate

Sheet steel, galvanised

Material of support
bracket

Steel, coated in black

Material of inlet nozzle

Sheet steel, galvanised

Number of blades

7

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP54

Insulation class

"B"

Humidity (F) /
environmental
protection class (H)

H1

Mounting position

Refer to product drawing

Condensation
drainage holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (programming)
- External release input
- Alarm relay
- Integrated PID controller
- Motor current limit
- PFC, passive
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical connection

Terminal box

Motor protection

Thermal overload protector (TOP) wired
internally

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

EAC; UL 1004-7 + 60730-1

Item no. 51232-5-9970 · ENG · Revision 210976 · Release 2020-03-27 · Page 5 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G310-BB49-02

Page 1: ...ry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is install...

Page 2: ...Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights...

Page 3: ...r 3 2 Nominal data Operating the device with all protective features in place Minding the operating instructions Improper use Using the device in the following ways is particularly prohibited and may...

Page 4: ...meter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm 4 Mounting position shaft horizontal install the support struts only vertically as shown in the view or rotor on bott...

Page 5: ...data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 22 1 kg Size 310 mm Motor size 112 Surface of rotor Coated in black Mater...

Page 6: ...ty of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with a Ssc...

Page 7: ...nto leads or wires Water enters at the cable end on the customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device only to circuits that...

Page 8: ...protection Due to the locked rotor protection the start up current LRA is equal to or less than the nominal current FLA 4 3 Connection in terminal box 4 3 1 Preparing connection lines for the connect...

Page 9: ...ip edge can be produced by fitting a cable tie directly in front of the cable gland for example 4 4 Factory settings Factory settings with which the device is pre set by ebm papst Control mode paramet...

Page 10: ...pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set sw...

Page 11: ...nce frequencies that may be present When regulating the speed pass through resonance ranges as quickly as possible or find another remedy Operation at excessive vibration levels can lead to premature...

Page 12: ...remove them afterwards Motor does not turn Mechanical blockage Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Importa...

Page 13: ...ingressed If cleaning does not eliminate vibration the fan may have to be re balanced In such cases please contact ebm papst The fan is provided with maintenance free ball bearings The lifetime lubri...

Page 14: ...ts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 4 3 Component disposal The products are...