Operating instructions

K3G280-PS10-J5

Translation of the original operating instructions

Product conforming
to standard

EN 61800-5-1; CE

Approval

CSA C22.2 no. 77 + CAN/CSA-
E60730-1; UL 1004-7 + 60730-1; CCC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

;

Use the device in accordance with its protection type.

Notes on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may vary during the production period.
Strength, dimensional stability and dimensional accuracy are not affected
by this.
The colour pigments of the paints used react perceptibly to UV light over
the course of time. This does not however have any influence on the
technical properties of the products. To prevent the formation of patches
and fading, the product is to be protected against UV radiation. Changes
in colour are not a reason for complaint and are not covered by the
warranty.

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

For depth of screw, see chapter 3.1 Product drawing

Strength class for
mounting screws

8.8

Any further mounting data required can be taken from the product
drawing or Section chapter 4.1 Connecting the mechanical system.

3.6 Transport and storage conditions

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

3.7 Electromagnetic compatibility

EMC interference
immunity

Acc. to EN 61000-6-2 (industrial
environment)

EMC interference
emission

Acc. to EN 61000-6-3 (household
environment), except EN 61000-3-2 for
professionally used devices with a total
rated power greater than 1 kW

If several devices are connected in parallel on the mains side,
so that the line current of the arrangement is in the 16-75 A
range, this arrangement conforms to IEC 61000-3-12, provided
that the short-circuit power S

sc

at the connection point of the

customer system to the public power grid is greater than or
equal to 250 times the rated output of the arrangement. It is the
responsibility of the installation engineer or operator/owner of the
device to ensure, if necessary after consultation with the
network operator, that this device is only connected to a
connection point with a S

sc

value that is greater than or equal to

250 times the rated output of the arrangement.

4. CONNECTION AND START-UP

4.1 Connecting the mechanical system

CAUTION
Cutting and crushing hazard when removing device
from packaging

→ Carefully remove the device from its packaging, only

touching the housing. Strictly avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

NOTE
Damage to device from vibration

Bearing damage, reduced service life
→ Forces or impermissibly high vibration levels must not be

transmitted to the fan from system components.

→ If the fan is connected to air ducts, it should isolated from

vibrations, for example using compensators or similar
elements.

→ Fasten the fan to the substructure without distorting it.

;

The fan may not be handled in the area around the inlet nozzle during
transport and installation.
There is a risk of damage to the impeller.

;

Check the device for transport damage. Damaged devices must no
longer be installed.

;

Install the undamaged device according to your application.

CAUTION
Possibility of damage to the device

Serious damage may result if the device slips during assembly.
→ Keep the device fixed in position at the installation location

until all attachment screws have been tightened.

The fan must not be strained on fastening.

4.2 Connecting the electrical system

DANGER
Electric voltage on the device

Electric shock
→ Always install a protective earth first.
→ Check the protective earth.

DANGER
Incorrect insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

requirements for voltage, current, insulation material, load etc.

→ Route cables such that they cannot be touched by any

rotating parts.

DANGER
Electrical load (>50 µC) between mains wire and
protective earth connection after switching of the supply
when switching multiple devices in parallel.

Electric shock, risk of injury
→ Make sure that sufficient protection against accidental contact

is provided.
Before working on the electrical connection, the
connections to the mains supply and PE must be shorted.

Item no. 54779-5-9970 · ENG · Revision 202174 · Release 2018-12-28 · Page 6 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G280-PS10-J5

Page 1: ...y out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installe...

Page 2: ...ding measures have to be taken by the user NOTE Electrical or electromagnetic interferences after integrating the device in installations on the customer s side Verify that the entire setup is EMC com...

Page 3: ...800 mbar to 1050 mbar Using the device in accordance with the permitted ambient temperature see chapter 3 6 Transport and storage conditions and chapter 3 2 Nominal data Operating the device with all...

Page 4: ...10 mm tightening torque 1 8 0 3 Nm 2 Cable diameter min 6 mm max 10 mm tightening torque 1 8 0 3 Nm use the provided seal Cable diameter min 4 mm max 7 mm tightening torque 1 8 0 3 Nm 3 Tightening tor...

Page 5: ...measurement configuration 3 4 Technical features Mass 9 7 kg Size 280 mm Motor size 84 Surface of rotor Coated in black Material of electronics housing Die cast aluminium Material of impeller PP plast...

Page 6: ...erator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with a Ssc value that is greater than or equal t...

Page 7: ...nect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided with a protectiv...

Page 8: ...actory settings Factory settings with which the device is pre set by ebm papst Control mode parameter set 1 PWM controlling Control mode parameter set 2 PWM controlling Fan device adress 01 Max PWM 10...

Page 9: ...in 10 mA reinforced insulation on mains side and basic insulation on control interface side 8 GND Signal ground for control interface SELV 9 RSA RS 485 interface for MODBUS RSA SELV 10 RSB RS 485 inte...

Page 10: ...ice via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the supply voltage When disconnecting be sure to disconnect the earth w...

Page 11: ...ient temperature too high Reduce the ambient temperature Let the device cool down To reset the error message switch off the mains supply voltage for a min of 25 s and switch it on again Alternatively...

Page 12: ...lopment stage ecological design technical safety and health protection are fixed criteria The following section contains recommendations for ecological disposal of the product and its components 6 4 1...

Page 13: ...ploying the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 54779 5 9970 ENG Revision 202174 Release 2018 12 28 Page 13 13 ebm papst Mulfing...