Operating instructions

K3G280-PS10-J5

Translation of the original operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All measures have the unit mm.

1

Cable diameter min. 8 mm, max. 12 mm, tightening torque 1.8±0.3 Nm (use the provided seal)
Cable diameter min. 4 mm, max. 10 mm, tightening torque 1.8±0.3 Nm

2

Cable diameter min. 6 mm, max. 10 mm, tightening torque 1.8±0.3 Nm (use the provided seal)
Cable diameter min. 4 mm, max. 7 mm, tightening torque 1.8±0.3 Nm

3

Tightening torque 3.5±0.5 Nm

4

Inlet nozzle with pressure tap (k-factor: 77)

Item no. 54779-5-9970 · ENG · Revision 202174 · Release 2018-12-28 · Page 4 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G280-PS10-J5

Page 1: ...y out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installe...

Page 2: ...ding measures have to be taken by the user NOTE Electrical or electromagnetic interferences after integrating the device in installations on the customer s side Verify that the entire setup is EMC com...

Page 3: ...800 mbar to 1050 mbar Using the device in accordance with the permitted ambient temperature see chapter 3 6 Transport and storage conditions and chapter 3 2 Nominal data Operating the device with all...

Page 4: ...10 mm tightening torque 1 8 0 3 Nm 2 Cable diameter min 6 mm max 10 mm tightening torque 1 8 0 3 Nm use the provided seal Cable diameter min 4 mm max 7 mm tightening torque 1 8 0 3 Nm 3 Tightening tor...

Page 5: ...measurement configuration 3 4 Technical features Mass 9 7 kg Size 280 mm Motor size 84 Surface of rotor Coated in black Material of electronics housing Die cast aluminium Material of impeller PP plast...

Page 6: ...erator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with a Ssc value that is greater than or equal t...

Page 7: ...nect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided with a protectiv...

Page 8: ...actory settings Factory settings with which the device is pre set by ebm papst Control mode parameter set 1 PWM controlling Control mode parameter set 2 PWM controlling Fan device adress 01 Max PWM 10...

Page 9: ...in 10 mA reinforced insulation on mains side and basic insulation on control interface side 8 GND Signal ground for control interface SELV 9 RSA RS 485 interface for MODBUS RSA SELV 10 RSB RS 485 inte...

Page 10: ...ice via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the supply voltage When disconnecting be sure to disconnect the earth w...

Page 11: ...ient temperature too high Reduce the ambient temperature Let the device cool down To reset the error message switch off the mains supply voltage for a min of 25 s and switch it on again Alternatively...

Page 12: ...lopment stage ecological design technical safety and health protection are fixed criteria The following section contains recommendations for ecological disposal of the product and its components 6 4 1...

Page 13: ...ploying the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 54779 5 9970 ENG Revision 202174 Release 2018 12 28 Page 13 13 ebm papst Mulfing...

Reviews: