3.2 Nominal data

Motor

M3G084-DF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Type of data definition

ml

Speed (rpm) / min

-1

3000

Power input / W

750

Current draw / A

3.3

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

45

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data in accordance with ecodesign regulation EU 327/
2011

Actual

Request 2015

01 Overall efficiency η

es

/ %

67.6

50

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

79.6

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
rating plate on the product.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
County court Stuttgart · HRA 590344
D-74673 Mulfingen

08 Type

K3G280-PR04-I2

09 Power input P

ed

/ kW

0.72

09 Air flow q

v

/ m³/h

2400

09 Pressure increase total p

sf

/

Pa

665

10 Speed (rpm) n / min

-1

2990

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data definition with optimum efficiency. The ErP data is determined using a motor-impeller

combination in a standardised measurement configuration.

3.4 Technical features

Mass

9.1 kg

Size

280 mm

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of impeller

PP plastic

Material of mounting
plate

Sheet steel, galvanised

Material of support
bracket

Steel, coated in black

Material of inlet nozzle

Sheet steel, galvanised

Number of blades

6

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 55

Insulation class

"F"

Humidity (F)/
environmental
protection class (H)

H1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Operation and alarm display
- Alarm relay
- Integrated PID controller
- Output limit
- Motor current limit
- PFC, active
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP) wired
internally

Cable exit

Variable

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

C22.2 Nr.77 + CAN/CSA-E60730-1;
UL 1004-7 + 60730; EAC

Item no. 54426-5-9970 · ENG · Revision 90170 · Release 2016-07-14 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G280-PR04-I2

Page 1: ...carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is ins...

Page 2: ...ystem machine wait until all parts have come to a standstill WARNING Rotating device Long hair dangling items of clothing jewellery and similar items can become entangled and be pulled into the device...

Page 3: ...ding the operating instructions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits...

Page 4: ...imped core end sleeves 2 Connection line PVC AWG22 5x crimped core end sleeves 3 Inlet nozzle 28004 2 4013 with pressure tap k factor 77 4 Mounting for inlet nozzle and FlowGrid Item no 54426 5 9970 E...

Page 5: ...ion with optimum efficiency The ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 9 1 kg Size 280 mm Surface of rotor Co...

Page 6: ...shoes and cut resistant safety gloves NOTE Damage to device from vibration Bearing damage reduced service life Forces or impermissibly high vibration levels must not be transmitted to the fan from sy...

Page 7: ...on the device The protective earth terminal is located on the housing and provided with a protective earth symbol and a hole 4 2 2 Idle current Because of the EMC filter integrated for compliance with...

Page 8: ...atus contact common connection contact rating 250 VAC 2A AC1 min 10 mA basic insulation on mains side and reinforced insulation on control interface side 2 8 0 10V yellow Analogue input 1 set value 0...

Page 9: ...ct the device from the supply voltage When disconnecting be sure to disconnect the earth wire connection last 5 INTEGRATED PROTECTIVE FUNCTIONS The integrated protective functions cause the motor to s...

Page 10: ...st NOTE High voltage test The integrated EMC filter contains Y capacitors Therefore the trigger current is exceeded when AC testing voltage is applied Test the device with DC voltage when you carry ou...

Page 11: ...ts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 4 3 Component disposal The products are...

Reviews: