background image

Operating instructions

K3G280-AU06-B6

Translation of the original operating instructions

Power cables

Cables for internal wiring

Electrolytic capacitors

Dispose of electronic components employing the proper procedures for
electronic scrap.

→ Please contact ebm-papst for any other questions on disposal.

Item no. 51318-5-9970 · ENU · Change 211092 · Approved 2020-05-20 · Page 14 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G280-AU06-B6

Page 1: ...permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devic...

Page 2: ...ntact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and...

Page 3: ...the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt depos...

Page 4: ...Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 2 Inlet ring with pressure tap k factor 93 3 Tightening torque 3 5 0 5 Nm Item no 51318 5 9970 ENU Change 211092 Approved 2020 05 20 Pag...

Page 5: ...ined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 11 5 kg Size 280 mm Motor size 84 Rotor surface Painted black Electronics housing material...

Page 6: ...ing Carefully remove the device from the packaging by grasping hold of the frame Never subject to any impact Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when unpacking device...

Page 7: ...l to or greater than that of the phase conductor We recommend the use of 105 C cables Ensure that the minimum cable cross section is at least AWG 26 0 13 mm Protective earth contact resistance accordi...

Page 8: ...cope of delivery into the terminal box Connect the wires to the corresponding terminals Use a screwdriver to do so When connecting ensure that no wire ends fan out Fig 3 Connecting wires to terminals...

Page 9: ...meter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 8 Save set value to EEPROM No Set value requirement Analog linear Direction of action parameter set 1 Positive heating Direction of ac...

Page 10: ...tion level KL3 2 8 GND Reference ground for control interface SELV KL3 3 7 0 10 V Control current sensor value input 0 10 VDC impedance 100 k use only as alternative to 4 20 mA input SELV KL3 4 10 V V...

Page 11: ...sively high vibration levels and possibly resonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or...

Page 12: ...am Motor electronics overtemperature Deficient cooling Improve cooling Let the device cool down To reset the error message switch off the line voltage for at least 25 s and then switch it on again The...

Page 13: ...n measurement Recommended every 6 months Clean impeller or replace device 6 4 Disposal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst opera...

Page 14: ...pose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 51318 5 9970 ENU Change 211092 Approved 2020 05...