ebm-papst G3G225-CD29-72 Operating Instructions Manual Download Page 7

Operating instructions

G3G225-CD29-72

Translation of the original operating instructions

4.2.2 Idle current

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and interference immunity), idle
currents in the mains cable can be measured even when the
motor is at a standstill and the mains voltage is switched on.

The values are typically in the range < 250 mA

At the same time, the effective power in this operating state
(operational readiness) is typically < 4 W.

4.2.3 Residual current operated device

If the use of a residual current device (RCD) is required in your
installation, only pulse current-sensitive and/or universal
residual current devices (type F or B) are permissible. Residual
current devices (RCD) cannot provide personal safety while
operating the device, as is also the case with frequency
converters. When the device power supply is switched on,
charging current pulses from the capacitors in the integrated
EMC filter can lead to the instant triggering of residual current
devices. We recommend the use of residual current circuit
breakers (RCCB) with an activation threshold of 300 mA and
delayed tripping (super-resistant, characteristic K).

4.2.4 Basic insulation of the alarm relay

As the alarm relay only has basic insulation (for TN/TT
systems) and function insulation (for systems with external
conductor earthing) with respect to the mains voltage, and not
double insulation like the rest of the interface, corresponding
precautions must be taken for industrial applications (EN 61800-
5-1).
→ The voltage switched by the alarm relay (e.g. 24 VDC)

must then have no electrical connection to the 10 V output, 0-
10 V control input and GND (electrically isolated interface).

4.2.5 Locked-rotor protection

Due to the locked-rotor protection, the start-up current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connection of the cables

External leads are brought out of device.

;

First connect the "PE" (protective earth) connection.

Connect the lines according to your application. When doing so,
observe chapter 4.5 Connection screen.

4.4 Factory settings

Factory settings with which the device is pre-set by ebm-papst.

Operation mode

PWM controlling

Group adress

01

Fan / device adress

01

Max. PWM / %

100

Min. PWM / %

0

Save set value to
EEPROM

No

Set value control

Analog

Control function

Positive (heating)

Item no. 56040-5-9970 · ENG · Revision 260973 · Release 2022-07-15 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for G3G225-CD29-72

Page 1: ...orised technical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic saf...

Page 2: ...fan is installed appropriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interferences after integrating the device in installations on the customer s side Veri...

Page 3: ...cularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that a...

Page 4: ...halogen free railway application EN 45545 5G 1 0 mm 5x core end sleeve 2 Connection line halogen free railway application EN 45545 3x 0 33 mm 3x core end sleeve Item no 56040 5 9970 ENG Revision 2609...

Page 5: ...e 2 2a motors completely integrated into a product 3 4 Technical features Mass 8 55 kg Size 225 mm Motor size 84 Surface of rotor Coated in black Material of electronics housing Die cast aluminium Mat...

Page 6: ...0 C between mains wire and protective earth connection after switching of the supply when switching multiple devices in parallel Electric shock risk of injury Make sure that sufficient protection agai...

Page 7: ...aracteristic K 4 2 4 Basic insulation of the alarm relay As the alarm relay only has basic insulation for TN TT systems and function insulation for systems with external conductor earthing with respec...

Page 8: ...inal operating instructions 4 5 Connection screen Item no 56040 5 9970 ENG Revision 260973 Release 2022 07 15 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 7938 81...

Page 9: ...e sure to disconnect the earth wire connection last 5 INTEGRATED PROTECTIVE FUNCTIONS The integrated protective functions cause the motor to switch off automatically in case of faults described in the...

Page 10: ...sedcleaning agents Do not use any pointed or sharp edged objects for cleaning Completely remove any cleaning agents used Immediately switch off and replace the device if severe corrosion is apparent a...

Page 11: ...ts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 3 3 Component disposal The products are...

Reviews: