background image

Operating instructions

A3G630-AQ37-21

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G112-GA

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

1000

Power consumption / W

720

Current draw / A

3.2

Max. back pressure / Pa

140

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

44.1

32.7

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

51.4

40

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

A3G630-AQ37-21

09 Power consumption P

ed

/ kW

0.69

09 Air flow q

v

/ m³/h

8080

09 Pressure increase total p

sf

/

Pa

124

10 Speed (rpm) n / min

-1

1005

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

9.8 kg

Size

630 mm

Motor size

112

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum, painted black

Blade material

Press-fitted sheet steel blank, sprayed
with PP plastic

Number of blades

5

Blade pitch

-5°

Airflow direction

V

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H2

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Alarm relay
- Motor current limitation
- PFC, active
- Soft start
- Control input 0-10 VDC
- Control interface with SELV potential
safely disconnected from supply
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1; CE

Approval

EAC; CCC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Item no. 50180-5-9970 · ENU · Change 205336 · Approved 2020-10-01 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for A3G630-AQ37-21

Page 1: ...specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associate...

Page 2: ...contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be eject...

Page 3: ...ng the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe...

Page 4: ...m 1 Direction of air flow V 2 Clearance for screw 12 16 mm 3 Cable PVC AWG18 5x crimped ferrules 4 Cable PVC AWG22 3x crimped ferrules Item no 50180 5 9970 ENU Change 205336 Approved 2020 10 01 Page 4...

Page 5: ...level The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 9 8 kg Size 630 mm Motor size 112 Rotor surface Painted black...

Page 6: ...only the blades near the hub Strictly avoid shocks Wear safety shoes and cut resistant safety gloves CAUTION The blades of the impeller could be damaged Carefully set down the fan on a soft surface M...

Page 7: ...ctive currents Because of the EMC filter integrated for compliance with EMC limits interference emission and immunity to interference reactive currents can be measured in the supply line even when the...

Page 8: ...ry settings made for the device by ebm papst Mode PWM control Group address 01 Fan device address 01 Max PWM 100 Min PWM 0 Save set value to EEPROM No Set value requirement Analog Direction of action...

Page 9: ...eak for failure 2 A max 250 VAC min 10 mA AC1 1 6 NC white 2 Floating status contact break for failure 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 k SELV 2 11 10 VDC red Voltage o...

Page 10: ...ound connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the event of the faults described in the table Fault Safety fea...

Page 11: ...y cleaning agents used If severe corrosion is visible on load bearing or rotating parts switch off the device immediately and replace it Repair of load bearing or rotating parts is not permitted Opera...

Page 12: ...nts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 3 3 Component disposal The products are...