background image

Operating instructions

A3G450-AO02-03

Translation of the original operating instructions

DANGER
Electrical charge (>50 µC) between phase conductor and
protective earth connection after switching off supply
with multiple devices connected in parallel.

Electric shock, risk of injury
→ Ensure sufficient protection against accidental contact.

Before working on the electrical hookup, short the supply
and PE connections.

CAUTION
Voltage

The fan is a built-in component and has no disconnecting switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole disconnection switch.

→ When working on the fan, secure the system/machine in

which the fan is installed so as to prevent it from being
switched back on.

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.

4.2.1 Requirements

;

Check whether the information on the nameplate matches the
connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

Protective earth contact resistance according to EN 60335

Compliance with the resistance specifications according to EN 60335 for
the protective earth connection circuit must be verified in the end
application. Depending on the installation situation, it may be necessary
to connect an additional protective earth conductor by way of the extra
protective earth terminal provided on the device.

4.2.2 Reactive currents

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and immunity to interference),
reactive currents can be measured in the supply line even
when the motor is at a standstill and the line voltage is switched
on.

The values are typically in the range < 50 mA

At the same time, the effective power in this operating state
(operational readiness) is typically < 2 W.

4.2.3 Residual current circuit breaker (RCCB)

If the use of a residual current device (RCD) is required in your
installation, only pulse-current sensitive and/or AC/DC-
sensitive residual current devices (type F or B) are
permissible. As with variable frequency drives, residual current
devices cannot provide personal safety while the device is
being operated. When the device power supply is switched on,
pulsed charging currents from the capacitors in the integrated
EMC filter can lead to the residual current devices tripping
instantly. We recommend the use of residual current circuit
breakers (RCCB) with a trip threshold of 300 mA and delayed
tripping (super-resistant, characteristic K).

4.2.4 Locked-rotor protection

Due to the locked-rotor protection, the starting current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connecting the cables

The device has external leads.

;

First connect the "PE" (protective earth).

Connect the cables according to your application. When doing so,
observe Chapter 4.4 Connection diagram.

Item no. 51639-5-9970 · ENU · Change 230625 · Approved 2022-03-02 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for A3G450-AO02-03

Page 1: ...Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observed when working on the d...

Page 2: ...fy that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entan...

Page 3: ... prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a life sustaining or life support function Conveying solids in the flow medium Painting the device Connection...

Page 4: ...1 Direction of air flow V 2 Max clearance for screw 10 mm 3 Cable PVC 3G AWG20 3x crimped splices 4 Cable PVC 4x AWG22 4x crimped splices Item no 51639 5 9970 ENU Change 230625 Approved 2022 03 02 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...quested from ebm papst If other air conduction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors completely integrated into a product 3 4 Technical description Weight 2 68 kg Size 450 mm Motor size ...

Page 6: ... it by only the blades near the hub Strictly avoid shocks Wear safety shoes and cut resistant safety gloves CAUTION The blades of the impeller could be damaged Carefully set down the fan on a soft surface Make sure the blades are not subjected to load Following installation make sure the impeller moves easily and that the blades of the impeller are not deformed or bent and do not catch at any poin...

Page 7: ...h connection circuit must be verified in the end application Depending on the installation situation it may be necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device 4 2 2 Reactive currents Because of the EMC filter integrated for compliance with EMC limits interference emission and immunity to interference reactive curren...

Page 8: ...12 PE green yellow Ground connection 2 0 10V PWM yellow 0 10 V PWM control input Ri 100 kΩ SELV 4 Tach white Tach output open collector 1 pulse per revolution Isink max 10 mA SELV 3 10 V red Fixed voltage output 10 VDC 3 Imax 10 mA short circuit proof power supply for ext devices e g pot SELV 1 GND blue Reference ground for control interface SELV Item no 51639 5 9970 ENU Change 230625 Approved 202...

Page 9: ...e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the event of the faults described in the table Fault Safety feature description function Rotor position detection error ...

Page 10: ...all bearings is designed for a service life of 40 000 hours If bearing replacement is necessary after that period contact ebm papst Adapt the maintenance intervals to the actual level of dust exposure 6 2 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing voltage is applied Test the device with DC voltage when you pe...

Page 11: ...inum Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets are used in external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electric...

Reviews: