Clear history data procedure
When a 900TS touchscreen notifies the user that that the memory is full, the logged data in the 900TS must be
cleared as described in this chapter.
NOTE
This procedure suitable for the 900TS
00
_0R and 900TS
02
_0R touchscreen!
NOTE
This procedure deletes the following data and preferences:
History graph
User preferences (unit selection, interface language, etc.)
Basic / Extended Modbus selection (if applicable to your project).
Clearing the memory (history data)
1.
Switch OFF the 900TS
(disconnect the power)
2.
Switch the power back ON the 900TS and enter the Start-up properties by touching the screen.
During the boot process the 900TS will first show the ebm-papst logo (with 6 loading animation blocks).
The following window (Fig. 1) will appear; press the screen to enter the ‘Start properties’ window (Fig. 2):
The ‘Start properties’ window will then appear (Fig. 2).
Retry Step 1 and 2 if the normal application starts in
stead of the ‘Start properties’ window.
3.
Open the ‘File operations’ window
Press the ‘File operations’ button (marked green in Fig. 2) to open the ‘Disk file operations’ window (Fig. 3):
Fig. 1
Fig. 2
NOTE
The touchscreen will continue to boot normally if
you do not press any of the buttons within 30
seconds. Return to step 1 if this situation occurs.