Operating instructions

8300100058

VBH0400CTRNS

Translation of the original operating instructions

4.3.3 Connect cables to terminals

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

;

Open the terminal box.

;

Remove the cap from the cable gland.

;

Only remove caps where cables are fed in.

Fig. 4: Installing the connectors in the terminal box. The connectors
must engage properly.

;

Depending on the cable diameter, the seals included in the terminal
box must be inserted into the cable gland if necessary.

;

Route the cable(s) (not included in the scope of delivery) into the
terminal box.

;

Ensure separate routing of the supply cable(s) and the cables for
status contact and control interface. Depending on the requirements for
the end device, the physical separation of these cables in the terminal
box may be mandatory. Use the partitions inside the terminal box as
an aid to routing for this purpose.

;

First connect the protective earth "PE". Tightening torque 3.5 ±0.4 Nm

;

Connect the cables to the corresponding terminals. Use a
screwdriver to do so. When connecting, make sure the wires do not
splay out. Insert the strands until they meet with resistance.

Fig. 5: Connection of cables at terminals

;

There must not be any tensile stress between the terminal and the
cable gland. The cable must be provided with strain relief.

;

The cable glands must be tight.

;

Fit the terminal box cover, making sure that the sealing surfaces are
clean.

;

Screw in the four screws (for tightening torque, see Chapter 3.1
Product drawing).

4.3.4 Cable routing

Water must be prevented from reaching the cable gland along the cable.

NOTE
Damage caused by moisture penetration.

Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable

glands, the cable should be routed in a U-shaped loop
wherever possible.

→ If this is not possible, a drip edge can be produced by

fitting a cable tie directly in front of the cable gland for example.

Item no. 1170000701 · ENU · Change 238377 · Approved 2021-12-16 · Page 9 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for 8300100058

Page 1: ...ice to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again foll...

Page 2: ...ct Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected an...

Page 3: ...ter 3 6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the dev...

Page 4: ...m The tightening torque is designed for PVC cables If the cable materials are different the tightening torque may have to be adjusted 3 Tightening torque 1 5 0 2 Nm 4 Inlet ring with pressure tap k fa...

Page 5: ...air conduction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation...

Page 6: ...angement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to...

Page 7: ...Check whether the information on the nameplate matches the connection data Before connecting the device make sure the power supply matches the device voltage Only use cables designed for the current...

Page 8: ...e cable used This must be checked by the user Fig 2 Recommended stripped lengths inside terminal box 1 supply line 2 control and relay line 4 3 2 Terminal connection data Supply line min max Rigid cab...

Page 9: ...ning torque 3 5 0 4 Nm Connect the cables to the corresponding terminals Use a screwdriver to do so When connecting make sure the wires do not splay out Insert the strands until they meet with resista...

Page 10: ...aracteristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Fan modulation level Characteristic curve...

Page 11: ...SELV D159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k 10KHz SELV Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 a...

Page 12: ...inal operating instructions 4 6 Equivalent circuit diagrams Item no 1170000701 ENU Change 238377 Approved 2021 12 16 Page 12 16 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0...

Page 13: ...1 Suppression of speed ranges Speed ranges in which the vibration velocity in the motor fan is too high must be avoided in continuous operation Excessive vibration velocities can be caused by resonan...

Page 14: ...rts automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Inadequate cooling Improve cooling Allow the devic...

Page 15: ...ening diameter on the motor support plate in the direction of the motor axis of rotation and perpendicular to this Fig 6 Example illustrating vibration measurement The arrangement of the sensors depen...

Page 16: ...dations for ecological disposal of the product and its components 6 5 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific lega...

Reviews: