Operating instructions

K3G560-PB31-61

Translation of the original operating instructions

4.5 Connection diagram

No.

Conn.

Designation

Function/assignment

CON1

L1, L2, L3

Power supply, phase, see nameplate for voltage range

PE

PE

Protective earth

CON2

RSA

RS485 interface for MODBUS, RSA; SELV

CON2

RSB

RS485 interface for MODBUS, RSB; SELV

CON2

GND

Reference ground for control interface, SELV

CON2

IO1

Function parameterizable (see “Optional interface functions” table)
Factory setting:
Digital input - high active, function: Disable input, SELV
- inactive: Pin open or applied voltage < 1.5 VDC
- active: applied voltage 3.5-50 VDC
Reset function: Triggering of error reset on change of state from "enabled" to "disabled"

CON2

IO2

Function parameterizable (see “Optional interface functions” table)
Factory setting:
Analog input 0-10 V / PWM, Ri=100 kΩ, function: Set value
Characteristic curve parameterizable (see input characteristic curve P1-IN), SELV

CON2

IO3

Function parameterizable (see “Optional interface functions” table)
Factory setting:
Analog output 0-10 V, max. 5 mA, function: Fan modulation level
Characteristic curve parameterizable (see output characteristic curve P3-OUT), SELV

CON2

Vout

Voltage output 3.3-24 VDC ±5%, Pmax=800 mW, voltage parameterizable
Factory setting: 10 VDC
short-circuit-proof, supply for external devices, SELV
alternatively: 15-50 VDC input for parameterization via MODBUS without line voltage

CON2

COM

Status relay, floating status contact, common connection, contact rating 250 VAC / 2 A (AC1) / min. 10 mA,
reinforced insulation on supply side and on control interface side

CON2

NC

Status relay, floating status contact, break for failure

LED

green: status = good, ready for operation
orange: status = warning
red: status = failure

P1-IN

Input characteristic curve

P3-OUT

Output characteristic curve

Item no. 56891-5-9970 · ENU · Change 200264 · Approved 2019-02-08 · Page 10 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G560-PB31-61

Page 1: ...a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installatio...

Page 2: ...rical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to b...

Page 3: ...stationary systems Performing all maintenance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter...

Page 4: ...ustrated or rotor on bottom rotor on top on request 2 Cable diameter min 4 mm max 10 mm tightening torque 2 0 3 Nm 3 Tightening torque 1 5 0 2 Nm 4 Inlet ring with pressure tap k factor 348 5 Mounting...

Page 5: ...n a standardized measurement setup 3 4 Technical description Weight 51 8 kg Size 560 mm Motor size 150 Rotor surface Painted black Electronics housing material Die cast aluminum Impeller material Shee...

Page 6: ...tion engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with an Ssc value greater tha...

Page 7: ...ustomer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched off with an all pole disconnect...

Page 8: ...onnections For tightening torques see Chapter 3 1 Product drawing NOTE Tightness and strain relief are dependent on the cable used This must be checked by the user Fig 2 Recommended stripped lengths i...

Page 9: ...ible a drip edge can be produced by fitting a cable tie directly in front of the cable gland for example 4 4 Factory settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM...

Page 10: ...eristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Fan modulation level Characteristic curve param...

Page 11: ...put Ri 100K characteristic curve parameterizable fPWM 1k 10KHz SELV D159 2 Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 active high digital input not active p...

Page 12: ...operating instructions 4 7 Equivalent circuit diagrams Item no 56891 5 9970 ENU Change 200264 Approved 2019 02 08 Page 12 16 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 793...

Page 13: ...sively high vibration levels and possibly resonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or...

Page 14: ...ply correct connection see connection diagram Broken motor winding Replace device Inadequate cooling Improve cooling Allow the device to cool down Ambient temperature too high Reduce the ambient tempe...

Page 15: ...ng If cleaning agents have been used rinse these off with clean water If severe corrosion is visible on load bearing or rotating parts switch off the device immediately and replace it Repair of load b...

Page 16: ...RNING Heavy parts of the product may drop off Some of the product components are heavy These components could drop off during disassembly This can result in fatal or serious injury and material damage...