background image

Basic Installation Concept & Accessories

Spec

Model

Voltage Input

Dimension

300-S

12VDC / 24VDC *

(L)170 x (W)35 x (T)22 (mm)

Current Draw

300mA / 150mA

12VDC / 24VDC
Power Supply

Self-tapping Screw x 5

Mounting Plate

Cable Wire

Armature Plate

Electromagnet

Guide Pin x2

Sexnut Bolt

Rubber

Washer

Metal

Washer

Armature
Screw

Fixing Screw

x2

12VDC / 24VDC
Power Supply

Wiring Instruction

1-2

Allen Wrench

T Handle Allen Key

(Not include in package)

* Note:

12VDC / 24VDC is pre-set

upon manufacture; once it

set, it cannot be changed.

Electromagnetic Lock

Installation Instruction Guide

(Intend for use in indoor dry location)

Notice: 
Model are Recognized to:
UL 294  

: Standard for Access Control System Units, 6th Ed.

ULC S533-15: Standard for Egress Door Securing &

Releasing Devices, 4th Ed.

Out Swing

EM Lock

Door
Frame

General Installation

Door Frame

Out-Swing

Glass
Door

EM Lock

Door

U1 Bracket For

   Glass Door

Door

Out-Swing

EM Lock

Door

Frame

ZL Bracket For
In-Swing Door

 LS Bracket For
Out-Swing Door

Door
Frame

Door

EM Lock

Self-tapping Screw

In-Swing

AH Bracket Fire Door Application

Out Swing

Door
Frame

Door

EM Lock

Armature Plate

Armature

Housing

      DSU Bracket For
Glass Frame & Glass Door

EM Lock

In-Swing

Glass
Door

Glass
Frame

Holding Force

Up to 300 lbs (Factory Tested)**

** Value not verified by UL.

General Installation Steps & Maintainance

1. 

2.

Close the door & position the template at the lock jamb side of the frame with a gap 10mm.

3.  Mark & drill holes according to template indications.
4.  Install the Armature Plate to the door.
5.  Loosely tighten screw through the adjustable slot on mounting plate to the door frame as indicated on

installation template.

6.  Make sure the mounting plate & armature align properly, then screw in the balance mounting screws.
7.

Use allen wrench to unscrew anti tamper nut and install the lock by tighten the fixing screws on the
mounting plate. Pull cable wire through frame to lock housing.

8.  Screw in the anti-tamper nuts to prevent unauthorized access and make sure to fully tighten the fixing

screw with proper tool "T" Handle Allen Key.

9.  Connect the power wires accordance with NFPA 101 & all wiring to be completed inside protect area.

10.  Typical wiring method which shall be in accordance with CSA C22.1, Canadian Electrical Code, Part I,

     Safety Standard for Electrical Installations, Section 32.

11.  It is recommended that to apply a light coat of silicon lubricant to the mating surface on a monthly

basis to prevent rust.

Trouble Shooting

1.

Sensor not functioning
-  Improper attachment of electromagnet and

armature plate

-  Modification of the PCB

2. Door not locked 

- Incorrect wiring or no power from power supply

3. Reduced holding force

- Poor contact of electromagnet and armature.
- Be sure armature is loose enough that it can fully

contact electromagnet along the entire length.

- Mating surface is dusty or damaged.
- Improper input voltage or wire size.

Performance Level

- Destructive Attack: Level I
- Line Security: Level I
- Standby Power: Level I
- Endurance 250,000 Cycles: Level IV

(Relay Source #2 & #3)

Remark:  All drawing shown are for illustration purpose only.

Actual product may vary due to product enhancement.

EISB-EMS-IG Ver.A  Publish:06.3.2020