2958 Operational Description (NFPA-101)
The 2958 operation complies with the following building and fire codes: NFPA 101; NFPA 1-UFC; UBC; IBC; IFC;
SBC; California Building Code. Listings: UL Listed: Special Locking Arrangements and Auxiliary Locks; California
State Fire Marshal (CSFM) Listed.
The door is normally closed & secured and/or latched. The model 2958 secures the door in the locked condition,
and the display shows the preset delay time.
Activation of the 2958 is made by releasing the door latch and applying up to 15 lbs. of pressure to the door,
giving a pre-activation warning tone. (A 1 or 2 second nuisance delay will prevent false activation of the alarm).
When the nuisance delay time has been exceeded, the 2958 begins the irreversible door release cycle. At this
time the display continues to count down, the verbal warning continues and an alarm output is provided to alert
personnel of an unauthorized exit.
The integral digital countdown display and voice commands inform the person intending to exit of the seconds
remaining to unlock. The 2958 will release the door after the 15 or 30 second delay cycle has expired, allowing
free egress. A steady warning tone with the voice command “Exit Now” will sound until the MagLock is reset by
authorized personnel.
2958 Operational Description (BOCA/Chicago)
The 2958 operation complies with BOCA National Building Code and the Chicago Building Code: UL Listed,
Special Locking Arrangements and Auxiliary Locks.
The releasing operation of the 2958 is the same as described above, with the exception that the door relocks
automatically 30 seconds after closure. Each time the door is open before 30 seconds has elapsed the relock
timer resets and relocks the door in 30 seconds.
INSTALLATION INSTRUCTIONS
DELAYED EGRESS MAGLOCK
2958 / 2958T
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
Application
When unauthorized egress is initiated, the 2958 delays egress through the door for 15 or 30 seconds.
Meanwhile, the person exiting must wait while personnel or security respond. An integral digital countdown
display and voice commands inform the person intending to exit of the seconds remaining to unlock. The door
unlocks after 15 or 30 seconds have elapsed, permitting egress. A signal from the fire/life safety system will
release the lock for uninhibited egress in an emergency.
Applications include:
·
Restricting the egress of patients for their own safety.
·
Restricting the egress of commercial center patrons for security application needs.
·
Controlling pedestrian traffic in transportation facilities, including airport jetways and tarmacs
California Building
Code Compliant
KEEP PUSHING. THIS DOOR
WILL OPEN IN 15 SECONDS.
ALARM WILL SOUND.
2958 Delayed Egress MagLock
Installation Instructions
S-EA00051
3/28/12
HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 ● (800) 325-9995
1