hager 2958 Delayed Egress MagLock Installation Instructions Manual Download Page 11

Standard Features

1650 lbs. Holding Force

15 or 30 Second Exit Delay when activated.

1 or 2 Second Nuisance Delay

75dB Alarm Tone with Digital Display & Selectable 

Voice Instruction

Choice of Activation Trigger:

-  Door Movement

-  Exit Device w/ REX Switch

-  Touch Sense Bar w/REX Switch

Vandal resistant Proximity Sensor Trigger

Auto Sensing 12/24VDC input power

Connection for Tandem Option (Pairs of Doors)

Optional Features

DPS

  Door Position Switch

MBS

  Bond Alert Sensor

ATS  

Anti Tamper Switch

Selectable Automatic & Manual Power-Up 

Feature

Auto Power-Up – Occurs when power is restored 

and/or the fire panel is restored.

Manual Power-Up – 

This is a UBC & California 

Building Code Compliant Feature – 

Only after power 

restoration and fire panel reset may the lock be reset 

manually at the opening.  Lock can be reset with the 

built-in reset key switch or, a key switch or keypad 

adjacent to the door.

Inputs & Outputs

REX Input 

Fire Alarm/Smoke Detection System Release

Remote Reset Input 

Remote Trigger Input 

Tandem/Slave Lock Input

IBO  – Instant Bypass Override

DPS – Door Position Status (Optional)

MBS – Magnetic Bond Status (Optional)

ATS – Anti-Tamper (Optional)

Alarm Output

Lock Status Relay Output 

-  Door Secure

-  Door Unlocked

Specifications

Interior Applications Only

Input Voltage Requirements:

Dual Voltage (Auto Sensing) – 

12/24 VDC (+/- 10%)

(Use with a UL 294 Standard Power Supply)

Power Consumption:

Standard Model (1650 lbs.) -

2958 – 820/500 mA@ 12/24 VDC

2958T – 1500/850 mA @ 12/24 VDC

Energy Saver (1200 lbs., “E” Option) – 

2958 – 452/274 mA@ 12/24 VDC

2958T – 660/686 mA @ 12/24 VDC

Size:  11"L x 2-3/4"H x 2-5/8"D

Lock Status Relay Rating:  1 Amp @ 30V resistive

Alarm Output Rating:  1 Amp @ 30V resistive

DPS Rating:  250 mA @ 30V resistive

BAS Rating:  250 mA @ 30V resistive

ATS Rating:  1 Amp @ 30V resistive

Operating Condition: 0-49 deg C, 85% RH 

                                                     (non-condensing)

  

Building & Fire Life Safety Code Compliant

2958ND

IBC

  International Building Code

IFC

  International Fire Code

NFPA 101

  Life Safety Code

NFPA 1, UFC

,  Uniform Fire Code

UBC

  Uniform Building Code

CBC

  California Building Code

SBC

  Standard Building Code

2958BD

BOCA

  National Building Code compliant

Chicago

 Building Code compliant

GWXT, GWXT7 - Auxiliary Locks - UL,cUL Listed

FWAX - Special  Locking Arrangements - UL Listed

Only the 2958 and the 2958T have 

been UL listed as Special Locking 

Arrangements to UL Standard 294, 

and NFPA 101.

2958 Delayed Egress MagLock

Installation Instructions

S-EA00051

3/28/12

HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 ● (800) 325-9995

11

Summary of Contents for 2958 Delayed Egress MagLock

Page 1: ...peration complies with BOCA National Building Code and the Chicago Building Code UL Listed Special Locking Arrangements and Auxiliary Locks The releasing operation of the 2958 is the same as described above with the exception that the door relocks automatically 30 seconds after closure Each time the door is open before 30 seconds has elapsed the relock timer resets and relocks the door in 30 secon...

Page 2: ...TED LINE Mark location five places 10 self dril tap screws provided for up to 1 8 thick metal applications Note Machine screws provided for applications with heavier gauge material Drill 21 and tap for 10 32 screw PLACE AGAINST LOCK JAMB FOR L H DOORS 1 4 DIA GUIDE PIN HOLE 9 16 DEEP PLACE AGAINST LOCK JAMB FOR R H DOORS PLACE AGAINST DOOR Center punch on mark 2958 Delayed Egress MagLock Installat...

Page 3: ...MAKE PROPER ADJUSTMENTS OF THE LOCK S POSITION PRIOR TO MARKING DRILLING AND TAPPING THE FOUR PERMANENT MOUNTING PLATE HOLES 1 2 DIA FOR WIRE First install mounting plate at two slot locations only and make proper adjustments before marking remaining five mounting hole locations FOLD ON DOTED LINE Mark location five places 10 self dril tap screws provided for up to 1 8 thick metal applications Not...

Page 4: ...ting screws using a soft hammer to avoid damage to the lock case ARMATURE MOUNTING INSTRUCTIONS Figure 2B HOLLOW METAL DOOR From sexnut side of door drill exactly 1 2 hole through one metal thickness only From armature side of door drill 5 8 hole to insert reinforcement tube Press in sexnut reinforcement tube all the way and mount armature to door using hardware provided per Figure 2B Figure 2A SO...

Page 5: ...TECTION SYSTEM IS CONNECTED TO FP INPUT Pg 8 3 or 5 conductors 8 or 10 conductors Power Supply To Fire Panel AC Mains 2 conductors PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS Key Switch or Access Control Optional To Smoke Detection System 2 conductors Digital Keypad 2958 Delayed Egress MagLock Installation Instructions S EA00051 2900 Series Power Supply Key Switch Reset Station Remote Speaker...

Page 6: ...rs Model 2958T REMOVE J6 ONLY IF A FIRE PANEL OR SMOKE DETECTION SYSTEM IS CONNECTED TO FP INPUT Pg 8 SLAVE To Smoke Detection System 2 conductors TB2 TB1 LOCK IN PWR TB5 TB6 TB4 TB3 DPS BAS TB7 NO C NC NO C NC NO C NC NO C Z4 D1 Z1 D2 R7 RLY1 J1 R9 C4 BAS DPS C1 J4 TB8 ATS TRIG OUT C NC NC NO NO C C NC NO C NO C NO C NO C NO C NC NO C NC BAS DPS RESET RM TRIG REX RED RLY GRN RLY LOCK FP PWR J6 J7...

Page 7: ... 2 Whenever the IBO input is closed and held the 2958 will instantly relock and rearm Egress is possible as the normal 15 30 sec delayed unlock 3 Releasing the IBO input will return the 2958 to the Bypass mode 4 Releasing the REX input will rearm the system 5 Upon power up you must manually reset the lock to activate the IBO input System Operation OPTIONAL RED GRN BLK WHT BLK BLU RED L3 OPTI ON C ...

Page 8: ... GRN RLY RED RLY RM TRIG RESET REX 12 VDC OR 24 VDC TO CLOSED FIRE SMOKE DETECTOR CONTACT SLAVE TANDEM LOCK POWER TERMINALS LOCK SECURE OUTPUT ALARM OUTPUT EXTERNAL TRIGGER SWITCH INPUT EXTERNAL RESET SWITCH INPUT REQUEST TO EXIT INPUT IBO INSTANT BYPASS OVERRIDE INPUT N O COM JUMPER J6 SEE PG 9 C NC NC NO NO C C NC NO C NO C NO C NO C NO C NC NOC NC BAS DPS RESET RM TRIG REX RED RLY GRN RLY LOCK ...

Page 9: ...ype is selectable to MSG1 or MSG2 MSG1 Female Voice Exit in 12 seconds facility staff has been notified Exit in 5 seconds exit now MSG2 Male Voice Exit in 12 seconds security has been alerted Exit in 5 seconds exit now Both messages repeat Exit now until the lock is reset WARNING CONTACT AUTHORITY HAVING JURISDICTION FOR APPROVAL PRIOR TO SELECTING DELAY TIME OR PWR UP SETTINGS OFF MESSAGE TYPE VO...

Page 10: ...se the door and apply power to the lock The digital display will show a two bars indicating that the lock is in the Manual Power Up mode Push on the door to verify that the door is unlocked Reset the lock at this time by turning the built in key switch clockwise or by triggering the remote reset input The lock should now secure the door and the LED display will show the delay time You may change t...

Page 11: ...ptional Alarm Output Lock Status Relay Output Door Secure Door Unlocked Specifications Interior Applications Only Input Voltage Requirements Dual Voltage Auto Sensing 12 24 VDC 10 Use with a UL 294 Standard Power Supply Power Consumption Standard Model 1650 lbs 2958 820 500 mA 12 24 VDC 2958T 1500 850 mA 12 24 VDC Energy Saver 1200 lbs E Option 2958 452 274 mA 12 24 VDC 2958T 660 686 mA 12 24 VDC ...

Page 12: ...CONDS PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS Systems Applications Reference Activation by a remote trigger for doors with or without latching hardware Activation by applying pressure to doors with latching hardware 2958 Delayed Egress MagLock ...