- 4 - 

Operation 
 

1. Before 

starting 

 

To rotate by hand, remove the motor end cap and 
turn slot on shaft end with a screwdriver. 

(1)  Turn pump by hand to check for smooth 

rotation. If movement is sluggish or uneven, 
components inside the pump may be rusted 
or the gland packing may be too tight. 

(2) 

 Remove the coupling bolts and briefly 

operate the motor alone to check rotation 
direction. The pump should rotate in a 

clockwise direction when seen from the 
motor side. 

    Replace coupling bolts after inspection is 

completed. 

(3)  Prime the pump. Operating the pump without 

prime will cause breakdown. 

    Open air-release valve and prime pump. If 

the piping is already full of water the pump 
can be supposed to be filled up to the 
discharge outlet, open the suction valve, 
discharge valve and air-release valve to 
prime. 

(4)  Rotate the pump by hand when priming to 

remove internal air from casing. 

 

 
 
 
 
 
 

2.  

Operation : 

 

 

 

CAUTION

 

 

Check rotation. Correct rotation is clockwise when viewed from top of motor. Pump should be  

 

started with gate valve closed, then the operator should open the valve gradually. 

 

 
(1)  Close the air-release valve and discharge 

valve after priming has been completed. If 
there is a suction valve, open completely. 

(2) 

Turn operation switch on and off two or three 
times to check operating condition. 

Attach 

shaft coupling guard after operation check 
has been completed.

 

(3)  Begin continuous operation and gradually 

open discharge valve. 

(4)   Check that pressure, current, vibration and 

noise (refer to 

Maintenance and service

) are 

at normal levels. Both the pressure gauge and 
compound gauge cocks should be kept closed 
except at specified times. Leaving them open 
may lead to malfunction. 

(5)   If there is no check valve on the discharge 

piping, close the discharge sluice valve slowly 
when stopping pump operation. Turn off 
operation switch after the sluice valve has 
been completely closed. 

(6)   Subsequent operation can proceed without 

checks, if all conditions are normal. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for FSA

Page 1: ...Volute Pump MODEL RQWHQWV 1 Safety Information and Introduction 1 2 Installation 2 3 Operation 4 4 Maintenance and Service 5 5 Replaceable Parts 6 6 Troubleshooting 7 7 Contruction 8 8 Disassembly an...

Page 2: ...16 3 kgf cm2 for standard flange JIS 16K RF Synchronous Speed 3000 min 1 1500 min 1 Installation Indoors Outdoors Impeller Enclosed Shaft seal Mechanical seal Gland Packing Sealing Self flushing Exte...

Page 3: ...ad of expelling it 4 To reduce effect of water hammer install such a device as a quick closing check valve 5 Suction system 1 The end of the suction piping should be submerged to a depth of at least t...

Page 4: ...Wiring 1 Refer to Fig 3 for correct wiring It is important that wiring be correct and that motor is properly grounded 2 Check the following points before turning on operation switch 1 Is the fuse the...

Page 5: ...ing 2 Operation CAUTION Check rotation Correct rotation is clockwise when viewed from top of motor Pump should be started with gate valve closed then the operator should open the valve gradually 1 Clo...

Page 6: ...bration may be due to conditions such as 15 incorrect centering defective piping or loose foundation bolts Inspect carefully In the event that special vibration control measures are necessary EBARA ha...

Page 7: ...5 FSKA FH 35 Gs 335 51x35x8 4 6307 ZZ 100x65 FSKA EA 262 40 Gs 335 56x40x8 4 6208 ZZ 100x80 FSGA FH 25 Gs 275 41x25x8 6305 ZZ 100x80 FSHA Gs 225 100x80 FSJA FH 35 Gs 275 100x80 FSGCA Gs 185 100x80 FSH...

Page 8: ...ion 3 Air pocket in suction piping 4 Suction height too high for pump 1 Prime sufficiently 2 Inspect repair suction piping shaft sealing 3 Reinstall piping 4 Re examine original plan Overloads over cu...

Page 9: ...oil Spring 111 1 Spring Holder Stainless Steel 1 No Part Name Material Qty 119 Gland Packing 4 or 5 091 Gland 085 Lantern Ring Bushing Bronze 1 No Part Name Material Qty 207 Plug Steel 111 Mechanical...

Page 10: ...rame and the deflector from the main shaft Mechanical seal type At this point in disassembly the fixed portion of the mechanical seal is attached to the casing cover and the rotating portion to the ma...

Page 11: ...10 MEMO...

Reviews: