background image

 

 

 
 

CS60 OWNERS MANUAL 

Drawing No.  :-  TPC302 
Issue :- 

Date :- 

12/07/04

 

REPAIRS 

 
 

 

1. 

Should an electrical component fail, consult the Factory Service Center to obtain the  

  proper 

replacement 

part. 

 
 

 

 

2. 

If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration  

 

 

technician to correct the fault.  Contact the Factory Service Center prior to initiating  

  this 

action. 

 

 

 

 

Any competent refrigeration technician will be able to service the equipment.  The 
following procedure must be used: 

 
 

 

a.  The source of the leak must be determined and corrected. 

 
 

 

b.  The machine should be thoroughly evacuated before recharging. 

 

 

 

 

c.  The unit must be recharged with refrigerant measured accurately by weight. 

 
 

 

d.  For evacuation and recharging of the machine, use the crimped and brazed 

charging stub attached to the side of the refrigerant compressor. 

 

 

 

 

The charging stub should be crimped and rebrazed after servicing.  

N

EVER

 

allow 

permanent service valves to be fitted to any part of the circuit.  Service valves 
may leak causing further loss of refrigerant gas. 

 

 

 

 

3. 

The refrigerant compressor fitted to the dehumidifier is a durable unit that should 
give many years of service.  Compressor failure can result from the machine losing its 
refrigerant gas.  The compressor can be replaced by a competent refrigeration 
technician.   

 
 

 

Failure of the compressor can be confirmed by the following procedure: 

 
 

 

a.  Establish that power is present at the compressor terminals using a voltmeter. 

 

 

 

b.  With the power disconnected, check the continuity of the internal winding by 

using meter across the compressor terminals.  An open circuit indicates that the 
compressor should be replaced. 

 

 

 

c.  Check that the compressor is not grounded by establishing that a circuit does not 

exist between the compressor terminals and the shell of the compressor. 

Summary of Contents for CS60

Page 1: ...CS60 OWNERS MANUAL Drawing No TPC302 Issue 1 Date 12 07 04 EBAC MODEL CS60 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL...

Page 2: ...quipped with a permanent drain The cooled air then passes through the hot condenser coil where it is reheated using the same energy removed during the cooling phase plus the additional heat generated...

Page 3: ...TIONS MODEL CS60 HEIGHT 13 25 336 55mm WIDTH 13 75 349 25mm DEPTH 20 25 514 35mm WEIGHT 62 83lbs 28 5 kg AIRFLOW 360 CFM EXTRACTION 56 Pints Per Day At 80 F 60 RH POWER SUPPLY 115V 60Hz 1 ph FINISH Po...

Page 4: ...eave the machine running for 15 minutes E Observe the evaporator coils through the rear upper grill to confirm frost operation i If the air temperature is below 80 F an even coating of frost should co...

Page 5: ...ore does not need oiling 3 To check the refrigerant charge run the unit for 15 minutes and briefly remove the top cover The evaporator coil should be evenly frost coated across its surface At temperat...

Page 6: ...of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak cau...

Page 7: ...s of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass valve 1 Conta...

Page 8: ...noid Valve 3020814 1 5 Filter Dryer 3020901 1 6 Compressor 3022163 1 7 Solenoid Coil 3030421 1 8 Capacitor 3030908 1 9 Humidistat 3035145 1 10 Mains Lead 3035148 1 11 Fan Motor 3035788 1 12 Relay 3036...

Page 9: ...H OF ANY WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THIS S...