Ebac CD100 Owner'S Manual Download Page 8

 
 
 
 

CD100 OWNERS MANUAL 

Drawing No.  :-  TPC112 
Issue :- 

Date :- 

20/06/03

 

REPAIRS 

 
 

 

1. 

Should an electrical component fail, consult the Factory Service Center to obtain the  

  correct 

replacement 

part. 

 
 

 

 

2. 

If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration  

 

 

technician to correct the fault.  Contact the Factory Service Center prior to initiating  

  this 

action. 

 

 

 

 

Any competent refrigeration technician will be able to service the equipment.  The 
following procedure must be used: 

 
 

 

a.  The source of the leak must be determined and corrected. 

 
 

 

b.  The machine should be thoroughly evacuated before recharging. 

 

 

 

 

c.  The unit must be recharged with refrigerant measured accurately by weight. 

 
 

 

d.  For evacuation and recharging of the machine, use the crimped and brazed 

charging stub attached to the side of the refrigerant compressor. 

 

 

 

 

The charging stub should be crimped and rebrazed after servicing.  

N

EVER

 

allow 

permanent service valves to be fitted to any part of the circuit.  Service valves 
may leak causing further loss of refrigerant gas. 

 

 

 

 

3.  The refrigerant compressor fitted to the dehumidifier is a durable unit that should 

give many years of service.  Compressor failure can result from the machine losing its 
refrigerant gas.  The compressor can be replaced by a competent refrigeration 
technician.   

 
 

 

Failure of the compressor can be confirmed by the following procedure: 

 
 

 

a.  Establish that power is present at the compressor terminals using a voltmeter. 

 

 

 

b.  With the power disconnected, check the continuity of the internal winding by 

using meter across the compressor terminals.  An open circuit indicates that the 
compressor should be replaced. 

 

 

 

c.  Check that the compressor is not grounded by establishing that a circuit does not 

exist between the compressor terminals and the shell of the compressor. 

Summary of Contents for CD100

Page 1: ...ER S MANUAL Ebac Commercial Ltd St Helens Trading Estate Bishop Auckland Co Durham DL14 9AD Telephone 01388 664400 Fax 01388 662590 Website www ebacuk com Ebac Industrial Products 704 Middle Ground Bo...

Page 2: ...ure which is collected and led away The cool air then passes the hot condenser where it is reheated With the addition of other radiated heat the air is discharged into the room at a higher temperature...

Page 3: ...S MODEL CD100 HEIGHT 400mm WIDTH 900mm DEPTH 500mm WEIGHT 50 Kg AIRFLOW 510 M3 hr POWER SUPPLY UK 220V 240V 1 ph 50Hz 60Hz USA 110V 120V 1 ph 50Hz 60Hz POWER 1 2kW max FINISH Vinyl coated steel REFRIG...

Page 4: ...in anyway WIRING Connect the power mains cable to a 13 Amp power supply As follows Brown Live Blue Neutral Green Yellow Earth ground DRAINAGE Connect a 15mm inside diameter hose to the water outlet pi...

Page 5: ...ning for 20 minutes the coils located above the drain tray will be evenly coated in frost If the ambient temperature is above 25 C the coils will be covered in water 4 After the machine has been runni...

Page 6: ...ear to be functioning correctly then refer to the repairs section Warnings Due to the high pressures within the refrigeration circuit under no circumstances must direct heat be applied to the evaporat...

Page 7: ...he coil approx 6 to avoid damaging the fins Alternatively vacuum clean the coils WARNING DO NOT STEAM CLEAN REFRIGERATION COILS 2 Check that the fan is firmly secured to the motor shaft and that the f...

Page 8: ...e of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak ca...

Page 9: ...efrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty Timer 2 Faulty bypass timer 1 Contact the...

Reviews: