Connection of the commands “START” and “PEDESTRIAN”
The connection of the opening command START can be
realized on every button or contact as soon as it is type
N.O. (normally opened). If you have several devices to
connect you need to connect them in parallel.
By using the clamps no. 17 and no. 24 you can connect a TIMER to program the openings of the gate. The con-
tact of your timer must be a type N.O. and must stay in a close mode the whole time the gate remains opened.
If there is an opening command connection on the clamp no. 17, connect in parallel.
The connection of the command for pedestrian
opening can be realized on every button or contact as
soon as it is type N.O. (normally opened).
4.12 Connection of LOCkING
Aside is the layout of the connection of the 12 Vac locking:
16 17 18 19 20 21 22 23 24 25
START-S4XL
Technical manual
-10-
4.13 Power supply of ACCESSORIES
17 18 19 20 21
28 29 30 31
+
-
TERMINAL 18-19
Tension:
24 Vac
Max Absorption: 300mA
TERMINAL 19-29
Tension: 12 Vac
Max Absorption: 600mA
TERMINAL 30-31
Tension: 24 Vdc
Max Absorption: 100mA
Below the layout of the connection for a correct power supply of the accessories. keep in mind that between
the clamps from no.19 to no. 29 there is a tension of 12 Vac.