background image

52

09/15 MN03407005Z-DE/EN

Summary of Contents for ZB65 Series

Page 1: ...3407005Z DE EN Handbuch Manual Motorschutzrelais ZB65 XTOB DC1 und ZB150 XTOB GC1 berlast berwachung von Ex e Motoren Motor protective relays ZB65 XTOB DC1 and ZB150 XTOB GC1 Overload monitoring of Ex...

Page 2: ...unter Verwendung elektronischer Systeme verarbeitet vervielf ltigt oder verbreitet werden nderungen vorbehalten All brand and product names are trademarks or registered trademarks of the owner concer...

Page 3: ...m eingebauten Zustand betrieben und bedient werden Before commencing the installation Disconnect the power supply of the device Ensure relosing interlock that devices cannot be accidentally restarted...

Page 4: ...EN Motorschutzrelais ZB65 XTOB DC1 und ZB150 XTOB GC1 berlast berwachung von Ex e Motoren 1 Motor protective relays ZB65 XTOB DC1 and ZB150 XTOB GC1 Overload monitoring of Ex e motors 31 Anhang Append...

Page 5: ...ais ZB65 XTOB DC1 und ZB150 XTOB GC17 Vorwort 7 Ger te bersicht 8 Ger tebeschreibung 9 berlastschutz mit Bimetallrelais 9 Strombereiche der Motorschutzrelais 10 Temperaturkompensation 12 Phasenausfall...

Page 6: ...69 ZB65 57 XTOB057DC1 70 ZB65 65 XTOB065DC1 71 ZB65 75 XTOB075DC1 72 ZB150 35 XTOB35GC1 ZB150 35KK XTOB035GC1S 73 ZB150 50 XTOB050GC1 74 ZB150 50KK XTOB050GC1S 75 ZB150 70 XTOB070GC1 ZB150 70KK XTOB0...

Page 7: ...diesem Handbuch werden Abk rzungen und Symbole eingesetzt die folgende Bedeutung haben X zeigt Handlungsanweisungen an Ex e Z ndschutzart Erh hte Sicherheit HFT Hardware Fehler Toleranz HM H chster m...

Page 8: ...lichkeit finden Sie auf den linken Seiten im Kopf die Kapitel berschrift und auf den rechten Seiten den aktuellen Abschnitt Ausnahmen sind Kapitel anfangsseiten und leere Seiten am Kapitelende j Gefah...

Page 9: ...daktions datum Seite Stichwort neu ge n dert ent f llt 09 15 15 Sicherheitstechnische Betrachtung j 21 Zulassungen j 27 Montage einer Plombierhaube j 01 11 allg Aufnahme der Eaton Typen j allg EEx e j...

Page 10: ...6 09 15 MN03407005Z DE EN...

Page 11: ...auftritt verhindert Die Motorschutzger te hierf r die sich selber nicht im Ex e Bereich befinden m ssen durch eine akkreditierte Zulassungsstelle zertifiziert sein F r Motoren in explosionsgef hrdeten...

Page 12: ...is ZB65 XTOB DC1 und ZB150 XTOB GC1 8 09 15 MN03407005Z DE EN Ger te bersicht Abbildung 1 Motorschutzrelais ZB65 XTOB DC1 Abbildung 2 Motorschutzrelais ZB150 XTOB GC1 Abbildung 3 Motorschutzrelais ZB1...

Page 13: ...ination mit einer Einzelaufstellung einzeln einsetzbar Die Relais ZB150 KK XTOB GC1S sind f r Einzelauf stellung konzipiert Einzelaufstellung Bei einer berlastausl sung schalten die Hilfsschalter 95 9...

Page 14: ...Q11 Motorsch tz M1 Motor Strombereiche der Motorschutzrelais Die Motorschutzrelais werden mit Hilfe der Strom Einstell scheibe auf den Motornennstrom eingestellt Mit entsprechenden Typen k nnen Motore...

Page 15: ...50 65 ZB65 751 XTOB075DC11 65 75 1 ohne ATEX Zulassung Typ Strombereich I A ZB150 35 XTOB035GC1 25 35 ZB150 50 XTOB050GC1 35 50 ZB150 70 XTOB070GC1 50 70 ZB150 100 XTOB100GC1 70 100 ZB150 125 XTOB125G...

Page 16: ...is ZB XTOB sind phasenausfall empfindlich Die Auslenkung aller drei Bimetalle wirkt auf eine Ausl sebr cke die bei Erreichen des Grenzwertes einen Sprungschalter umschaltet Gleichzeitig verschieben al...

Page 17: ...tellung Automatik fallen die Kontakte nach dem Abk hlen der Bimetalle automatisch zur ck in der Hand stellung muss die Ausl sung vor Ort am Motorschutzrelais quittiert werden h Soll mit einem Motorsch...

Page 18: ...s Dr cken der Testtaste ffnet den ffner 95 96 Nach dem Loslassen f llt der ffner wieder zur ck Diese Funktion kann zum manuellen Ausschalten des Motors genutzt werden Das Ziehen der Testtaste f hrt zu...

Page 19: ...Fehler Toleranz HFT 0 siehe EN 61508 Teil 1 Tabelle 3 und EN 61508 Teil 2 Tabelle 2 f r die Motorschutzrelais bei einer Umgebungstemperatur von 55 C Motorschutz berlast Sicherheitsintegrit tslevel Ver...

Page 20: ...ie mittlere Betriebsdauer zwischen zwei Ausf llen MTBF betr gt 43 Jahre F r die sicherheitsbezogenen Teile von Steuerungen nach EN ISO 13849 wurden bei einer Umgebungstemperatur von 55 C folgende Date...

Page 21: ...r sich alleine nicht sicher Sie erlangen die Explosionssicherheit durch zus tzliche Ma nahmen bei der Installation durch eine zweckentsprechende Auswahl und Einsatzbedingungen PTB Pr fregeln unter an...

Page 22: ...15 MN03407005Z DE EN Beispiel IA IN 6 tE 10 s Abbildung 7 Ausl sekennlinie des Motorschutzrelais Der Motor wird zuverl ssig gesch tzt 1 0 1 0 2 0 4 0 6 0 8 1 2 4 6 8 10 20 40 1 2 4 6 8 10 2 3 4 5 6 7...

Page 23: ...XTOB DC1 in Direktanbau oder Einzel aufstellung i Vorsicht Zum Schutz von Ex e Motoren ist nach EN 60947 4 1 nur die Zuordnungsart 2 zul ssig Typ Sch tz Sicherung gG gL A Zuord nungsart 1 1 Zuord nun...

Page 24: ...80F 250 160 ZB150 100 XTOB100GC1 DILM95 XTCE095F 315 200 ZB150 125 XTOB125GC1 DILM115 XTCE115G 315 250 ZB150 150 XTOB150GC1 DILM150 XTCE150G 315 250 ZB150 175 XTOB175GC1 DILM170 XTCE170G 315 250 1 nac...

Page 25: ...linie 94 9 EG ATEX 100a zum Schutz von Ex e Motoren Au erdem k nnen nach EN 60079 14 Motoren in den Zonen 21 und 22 Bereiche mit brennbarem Staub gesch tzt werden Die Motorabgangsverdrahtung ist nach...

Page 26: ...22 09 15 MN03407005Z DE EN...

Page 27: ...06Z vormals AWA2300 2115 j Gefahr F r den Explosionsschutz ist nur ein manuelles R ck setzen Einschalten nach dem Abk hlen der Bimetalle oder ein automatisches Zuschalten ber eine Steuerungsverrie gel...

Page 28: ...tungssch tz M1 Motor Die Selbsthaltung des Leistungssch tzes Q11 verhindert einen automatischen Wiederanlauf Die Funktion Fernreset bzw Remote kann erzielt werden indem das Motorschutzrelais auf AUTO...

Page 29: ...Tabelle 6 Direktanbau Tabelle 7 Einzelaufstellung X Montieren Sie die Ger te wie in den nachfolgenden Abbildungen angegeben Motorschutzrelais Sch tz ZB65 XTOB DC1 DILM40 XTCE040D ZB65 XTOB DC1 DILM50...

Page 30: ...tage ZB65 XTOB DC1 Die Einzelaufstellungen ZB65 XEZ XTOBXDIND k nnen auf einer Hutschiene oder direkt auf der Montageplatte montiert werden Abbildung 10 Montage ZB150 XTOB GC1 DIL XTCE ZB65 XTOB DC1 Z...

Page 31: ...rlastein stellung vorgenommen werden kann Dies reduziert die Gefahr vor Manipulation und erh ht die Betriebssicherheit Motorschutzrelais in Geh usen oder hinter Abdeckungen k nnen bequem mittels Taste...

Page 32: ...Hierbei ist nur ein Leiter pro Klemmraum zugelassen a Abb 2 auf Seite 8 1 3 Hauptstrombahnen Hilfsstrombahnen ZB65 XTOB DC1 ZB150 XTOB GC1 95 96 97 98 1 x 1 16 1 x 4 16 1 x 0 75 4 mm2 2 x 1 16 2 x 4 1...

Page 33: ...d einer Handr ck setzung H zu w hlen Abbildung 13 Schaltm glichkeiten mit Wahlknopf Reset Die Stellung H verhindert einen automatischen Wieder anlauf und ist werksseitig bei den Motorschutzrelais vorg...

Page 34: ...ste Test Ein Ziehen der Taste hat das ffnen des Hilfskontaktes 95 96 zur Folge und kann zum Abschalten des Sch tzes genutzt werden Im stromlosen Zustand kann durch das Ziehen der Taste die Funktion be...

Page 35: ...XTOB GC1 overload relays37 Foreword 37 Device overview 38 Description of device 39 Overload protection with current transformer operated overload relay 39 Current ranges of the overload relays 40 Temp...

Page 36: ...69 ZB65 57 XTOB057DC1 70 ZB65 65 XTOB065DC1 71 ZB65 75 XTOB075DC1 72 ZB150 35 XTOB35GC1 ZB150 35KK XTOB035GC1S 73 ZB150 50 XTOB050GC1 74 ZB150 50KK XTOB050GC1S 75 ZB150 70 XTOB070GC1 ZB150 70KK XTOB07...

Page 37: ...Abbreviations and symbols Symbols used in this manual have the following meanings X indicates actions to be taken Ex e Type of protection Increased Safety HFT Hardware Fault Tolerance HM Highest poss...

Page 38: ...t hand pages you will find the Chapter heading at the top of right hand pages the current Section heading exceptions are the first pages of Chapters and empty pages at the end of Chapters i Caution wa...

Page 39: ...tion date Page Keyword New Modi fied Omit ted 09 15 45 Safety analysis j 51 Approvals j 57 Mounting a sealable shroud j 01 11 General Inclusion of Eaton models j General EEx e now Ex e j 37 Notes abou...

Page 40: ...36 09 15 MN03407005Z DE EN...

Page 41: ...mal operating conditions The motor protective devices for this that are themselves not located in the Ex e area must be certified by an accred ited certification body For for motors in explosive dust...

Page 42: ...OB DC1 and ZB150 XTOB GC1 overload relays 38 09 15 MN03407005Z DE EN Device overview Figure 1 ZB65 XTOB DC1 overload relays Figure 2 ZB150 XTOB GC1 overload relays Figure 3 ZB150 KK XTOB GC1S overload...

Page 43: ...1 relays can also be operated indivi dually in combination with a separate mounting The ZB150 KK XTOB GC1S relays are designed for separate mounting Separate positioning In the event of an overload tr...

Page 44: ...ntactor M1 Motor Current ranges of the overload relays The overload relays are set to the rated current of the motor by means of a current setting dial The corresponding types can be used to monitor m...

Page 45: ...B65 751 XTOB075DC11 65 75 1 without ATEX accreditation Type Current range I A ZB150 35 XTOB035GC1 25 35 ZB150 50 XTOB050GC1 35 50 ZB150 70 XTOB070GC1 50 70 ZB150 100 XTOB100GC1 70 100 ZB150 125 XTOB12...

Page 46: ...nsi tive The deflecting action of all three bimetallic releases is directed towards a tripping bridge that switches over a snap action switch when the limit value is reached At the same time all three...

Page 47: ...automatically fall back after the bimetallic releases have cooled down whereas in manual mode the tripping must be acknowledged locally on the overload relay h When a ZB XTOB overload relay is to be...

Page 48: ...the button is pressed the N C contact 95 96 opens It falls back again when the button is released This function can also be used to switch off the motor manually Pulling the Test button will trip the...

Page 49: ...dware fault toler ance HFT of 0 see Table 3 in EN 61508 Part 1 and Table 2 in EN 61508 Part 2 for the overload relays at an ambient temperature of 55 C Motor protection overload Safety integrity level...

Page 50: ...he mean lifespan between two failures MTBF is 43 years For the safety related parts of control systems as per EN ISO 13849 the following data was determined at an ambient temperature of 55 C Size Valu...

Page 51: ...A However Ex e motors are not safe on their own Explosion safety can only be achieved by taking additional measures during installation and by selecting appropriate operational conditions PTB testing...

Page 52: ...15 MN03407005Z DE EN Example IA IN 6 tE 10 s Figure 7 Tripping characteristic of the overload relay The motor is reliably protected 1 0 1 0 2 0 4 0 6 0 8 1 2 4 6 8 10 20 40 1 2 4 6 8 10 2 3 4 5 6 7 8...

Page 53: ...irect mounting or individual installation i Warning According to EN 60947 4 1 only type of coordination 2 may be used for the protection of Ex e motors Type Contactor Fuse gG gL A Type of coor dinatio...

Page 54: ...ZB150 100 XTOB100GC1 DILM95 XTCE095F 315 200 ZB150 125 XTOB125GC1 DILM115 XTCE115G 315 250 ZB150 150 XTOB150GC1 DILM150 XTCE150G 315 250 ZB150 175 XTOB175GC1 DILM170 XTCE170G 315 250 1 According to I...

Page 55: ...ives for the protection of Ex e motors Furthermore motors can be explosion protected in zones 21 and 22 areas with combustible dusts in compliance with EN 60079 14 The wiring of the motor feeder must...

Page 56: ...52 09 15 MN03407005Z DE EN...

Page 57: ...03407006Z former AWA2300 2115 j Danger For explosion protection it is only permissible to reset switch on the motor protection relay manually after the bimetallic release has cooled down or automatica...

Page 58: ...actor relay M1 Motor The latching function of the Q11 contactor relay prevents an automatic restart The remote reset remote function can be implemented by setting the overload relay to AUTO M1 M U V W...

Page 59: ...nstalled individually Table 6 Direct mounting Table 7 Separate mounting X Mount the devices as shown in the figures below Overload relays Contactor ZB65 XTOB DC1 DILM40 XTCE040D ZB65 XTOB DC1 DILM50 X...

Page 60: ...g the ZB65 XTOB DC1 The single mount assemblies ZB65 XEZ XTOBXDIND can be mounted individually on DIN rail or directly on a mounting panel Figure 10 Mounting the ZB150 XTOB GC1 DIL XTCE ZB65 XTOB DC1...

Page 61: ...t with sealing wire This will reduce the risk of tampering and improve operational safety and reliability Overload relays in enclosures or behind covers can be conveniently operated by using M22 DZ pu...

Page 62: ...one conductor may be termi nated in each terminal clamp a Fig 2 on Page 38 1 3 Main circuits Auxiliary circuits ZB65 XTOB DC1 ZB150 XTOB GC1 95 96 97 98 1 x 1 16 1 x 4 16 1 x 0 75 4 mm2 2 x 1 16 2 x...

Page 63: ...ector button Figure 13 Switching options of the Reset selector button The factory set position H on the overload relay prevents automatic restarts In position H the relay must be reset manually after...

Page 64: ...of the Test button The auxiliary contact 95 96 is opened by pulling the Test button and can thus be used to switch off the contactor relay The function of both auxiliary contacts can be tested in curr...

Page 65: ...en Tabelle 11 zu entnehmen For information on the assignment of values to the relevant types please refer to table 11 Ith 6 A Uimp 6000 V Ue 690 V A gL gG A gL gG Type 2 max Type 1 max IEC EN 60947 5...

Page 66: ...Table 11 Werte der einzelnen Typen Values of the various types A B D F ZB65 10 XTOB010DC1 50 25 ZB65 16 XTOB016DC1 63 35 ZB65 24 XTOB024DC1 63 50 ZB65 40 XTOB040DC1 125 63 ZB65 57 XTOB057DC1 160 80 ZB...

Page 67: ...lle 12 zu entnehmen For information on the assignment of values to the relevant types please refer to table 12 Ith 6 A Uimp 6000 V Ue 690 V A gL gG A gL gG Type 2 max Type 1 max IEC EN 60947 5 1 IEC E...

Page 68: ...en Typen Values of the various types A B D F ZB150 35 XTOB035GC1 125 100 ZB150 50 XTOB050GC1 160 125 ZB150 70 XTOB070GC1 250 160 ZB150 100 XTOB100GC1 315 200 ZB150 125 XTOB125GC1 315 250 ZB150 150 XTO...

Page 69: ...Ausl sekennlinien Tripping characteristics 65 09 15 MN03407005Z DE EN Ausl sekennlinien Tripping characteristics...

Page 70: ...stemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase...

Page 71: ...NM HM Umgebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase c 3...

Page 72: ...temperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase...

Page 73: ...HM Umgebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase c 3 pha...

Page 74: ...ngstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 pha...

Page 75: ...HM Umgebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phas...

Page 76: ...emperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d...

Page 77: ...Bereich Range 25 35 A NM HM Umgebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM...

Page 78: ...temperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase...

Page 79: ...A NM HM Umgebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase c...

Page 80: ...50 70 A NM HM Umgebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 ph...

Page 81: ...A NM HM Umgebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeitTripping time t s NM HM 3 phase a 2 phase c 3...

Page 82: ...ebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2...

Page 83: ...S Bereich Range 95 125 A NM HM Umgebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM H...

Page 84: ...ebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2...

Page 85: ...50 A NM HM Umgebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase...

Page 86: ...ebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2...

Page 87: ...75 A NM HM Umgebungstemperatur Ambient temperature 20 C Ausl seklasse Tripping class 10 A Toleranzbereich Tolerance range g20 Einstellung Setting Ausl sezeit Tripping time t s NM HM 3 phase a 2 phase...

Page 88: ...mplies with the provisions of Council directive s RF 1R Wir We Eaton Industries GmbH Hein Moeller Str 7 11 53115 Bonn Germany ZB65 Niederspannungsrichtlinie g ltig bis 19 April 2016 Low Voltage Direct...

Page 89: ...duktfamilie und in Kombination mit den darunter folgenden Produkten The declaration of conformity applies to the following types within the product family and in combination with products listed below...

Page 90: ...mplies with the provisions of Council directive s RF 1R Wir We Eaton Industries GmbH Hein Moeller Str 7 11 53115 Bonn Germany ZB150 Niederspannungsrichtlinie g ltig bis 19 April 2016 Low Voltage Direc...

Page 91: ...ende Typen der Produktfamilie und in Kombination mit den darunter folgenden Produkten The declaration of conformity applies to the following types within the product family and in combination with pro...

Page 92: ...88 09 15 MN03407005Z DE EN...

Reviews: