5 Installation
5.3 Interfaces
Touch display XV-102
10/2020 MN04802004Z-EN
Eaton.com
31
Radio interference
suppression filter for the
24 V DC supply
Additional interference filters must be installed for the power supply in order to adhere to the EMC B
provisions.
Integrate a radio interference suppression filter into the wiring.
Depending on the output, the following filters can be used:
XT-FIL-1 radio interference suppression filter for 24 V DC supply up to 2.2 A (Eaton article no.
285316)
or
XT-FIL-2 radio interference suppression filter for 24 V DC supply up to 12 A (Eaton article no.
118980)
Fig.. 13 Power supply with EMC filter
Grounding is ensured either by using
the filter's integrated contact fields onto a grounded metal plate
or using
a separate line to the filer's PE connection.
Depending on the current consumption or configuration, several filters may be used as well.
5.2.2 Conditions for marine approval (DNV GL),
5.4.2 Screening the communication cables used,
~
=
L1
L2
L3
N
PE
24 V 0 V
U
POW
XT-FIL-1/2
24 V 0 V
24 V 0 V
U
AUX
XV-102
24 V
0 V
24 V
0 V
24 V 0 V
PE
...