5 Installation
5.3 Interfaces
42
Touch display XV-102
10/2020 MN04802004Z-EN
Eaton.com
Wiring
Screened twisted-pair cables must be used.
Tab. 18 Cable specifications
The maximal baud rate depends on the cable length
Tab. 19 Relationship of cable length / baud rate
Cable specifications
Rated surge impedance
120
Permissible surge impedance
108…132
Capacitance per unit length
< 60 pF/m
Core cross-section / max. cable length
0.25 mm
2
/ 100 m
0.34 mm
2
/ 250 m
0.75 mm
2
/ 500 m
Cable length
Max. baud rate
25 m
1000 kbit/s
50 m
800 kbit/s
100 m
500 kbit/s
250 m
250 kbit/s
500 m
125 kbit/s
500 m
100 Kbit/s (adjustable via software)
1000 m
50 kbit/s
2500 m
20 kbit/s
5000 m
10 kbit/s
The use of repeaters is recommended for cable lengths over 1000 m. Repeaters can
also be used to implement galvanic isolation. Refer to the documentation of the re-
peater manufacturer for more specific details.
Observe the recommendations of CiA (CAN in Automation).
When preparing the cables, ensure that there is a low-resistance connection between
the cable screen and the connector casing (