10/10 MN05003004Z-EN
Updating the operating system
(OS)
23
Wait for the following display.
X
In this window click the Exit button.
After download of the OS into the PLC the “Communication
interrupted” message may appear as the PLC is rebooted after
every download of the OS. Renewed login is required after each
reboot.
As soon as you have logged on, the following message appears:
“No program on the PLC! Should the new program be loaded?
The program is loaded after you have acknowledged the question
with “Yes”. You can then create the boot project.
Transferring the operating system from the PC into the
MMC
If an OS is loaded into the MMC, the OS and the boot project on
the MMC and the user program in the PLC are deleted. The
procedure is similar to the description in section “Transferring the
operating system from the PC to the PLC” on page 22.
Transferring the operating system from the MMC into the
PLC
Switch the PLC off and on. The transfer can take more than 30
seconds as the CPU must be booted several times.
Do not interrupt the process, e.g. by switching off the supply
voltage!
Update of further XC100 PLCs
If you wish to transfer the new operating system to further PLCs,
insert the MMC into the PLC, which also features an OS from
V03.03 or higher. The OS of the PLC is updated during the switch
on process and a boot project is loaded into the PLC.
Figure 25: Warning during download
Figure 26: OS successfully transferred to the PLC
Summary of Contents for XC200 Series
Page 4: ...II ...
Page 8: ...10 10 MN05003004Z EN 4 ...
Page 28: ...10 10 MN05003004Z EN 24 ...
Page 50: ...10 10 MN05003004Z EN 46 ...
Page 74: ...10 10 MN05003004Z EN 70 ...