Installation instructions
WaveLinx Wireless Area Controller (WAC)
8. After all WaveLinx devices have joined the Construction Group and illustrated the above behavior.
●
●
Press the “PAIR” button on the WAC a second time to leave the Construction Grouping mode,
●
●
The WAC will leave Construction Grouping automatically after 30 minutes if the “PAIR” button is not pressed a second
time.
●
●
The IEEE 802.15.4 wireless network LED on the WAC will be ON
9. After leaving the Construction Group mode the WaveLinx devices will behave in the following manner.
●
●
Luminaires with integrated sensors
●
●
Luminaire dims to 75%
●
●
All luminaires turn ON when the first occupancy sensor senses motion
●
●
All luminaires turn OFF when the last occupancy sensor times out unoccupied
●
●
All wallstations in the default area control all luminaires together.
●
●
All integrated sensors, Tile Mount and Ceiling sensors create an occupancy group
●
●
Tile Mount Sensor.
●
●
Connected luminaire dims to 75%
●
●
All luminaires turn ON when the first occupancy sensor senses motion
●
●
All luminaires turn OFF when the last occupancy sensor times out unoccupied
●
●
All wallstations in the default area control all luminaires together.
●
●
All integrated sensors, Tile Mount and Ceiling sensors create an occupancy group
●
●
Relay with 0-10V
●
●
Connected luminaires dim to 75%
●
●
All wallstations in the default area control all luminaires together.
●
●
All luminaires turn ON when the first occupancy sensor senses motion
●
●
All luminaires turn OFF when the last occupancy sensor times out unoccupied
●
●
Relay turns ON/OFF based on occupancy
●
●
Receptacle
●
●
The controlled outlet will turn ON/OFF based on occupancy
●
●
Wallstation
●
●
All wallstations in the default area will control all luminaires in the default area based on out-of-the-box scene
definitions.
●
●
Ceiling Sensor
●
●
The LED on the sensor will flash when detecting occupancy
●
●
All integrated sensors, Tile Mount and ceiling sensors create an occupancy group
Connecting the Wireless Area Controller to the Building LAN
1. Wired Connection - Building LAN connection
●
●
Connect the WAC to the building PoE switch or PoE injector into the normal network.
●
●
Physical connection to the building LAN and receiving an IP address will automatically disable the wireless connection
method
●
●
WAC’s will automatically receive a DHCP IP address when connected to the building LAN
●
●
WAC device name will be: Eaton-xxxxxxxxxxxx on the building network
●
●
(where **** are all twelve characters of the unit MAC address found on the label at the bottom front of the WAC
plus 1)