![background image](http://html1.mh-extra.com/html/eaton/w-vacimb/w-vacimb_manual_2353203036.webp)
65A7320H01
36 of 41
Appendix A: Wiring Locations
Figure 28: Graphical locations of each wire.
Terminal Position
Old CODE
New CODE 2013+
Purpose
1
D1
X11:25
M1:1
Motor Power Supply (Hi)
2
C9
Q1.1:9
X11:7
Normally Open Relay 1 (Hi)
3
C13
Q1.1:13
X11:9
Normally Open Relay 2 (Hi)
4
C7
Q1.1:7
X11:23
Normally Closed Relay (Hi)
5
H4
X11:44
Y6:2
UVR Return (Lo)
6
P2
X11:14
U2:2
Close Coil Return (Lo)
7
F22
M1.2:22
X11:35
Motor Return (Lo)
8
C2
Q1.1:2
X11:30
Trip Coil Return (Lo)
9
H3
X11:2
Y6:1
UVR Power Supply (Hi)
10
P1
X11:4
U2:1
Close Coil Power Supply (Hi)
11
P7
X11:31
U2:7
Trip Coil Power Supply (Hi)
12
C10
Q1.1:10
X11:17
Normally Open Relay 1 (Lo)
13
C14
Q1.1:14
X11:19
Normally Open Relay 2 (Lo)
14
C8
Q1.1:8
X11:33
Normally Closed Relay (Lo)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Note: The “X11” designation refers to the secondary connector. For example, “X11:25” is the 25