65A7320H01
35 of 41
QUALITY CHECK
Visually inspect the breaker for defects.
Make sure all of the electrical connections are correctly secured.
Make sure all of the electrical connections are in accordance to the
wiring schematic.
Make sure all of the bolted connections that were added as a part of
this procedure are properly tightened.
Electrically test the operation of the breaker to make sure the
modifications were correctly done and that the breaker properly
operates. Electrically operate the breaker five times for a charge -
open - close type operation.
Inspect the operation of the large black closing mechanism spring to
make sure that it does not hit the modified wiring harness on the left
side of the mechanism side sheet. The spring should have 0.5” or
more clearance during opening or closing.
Make sure the front cover is properly mounted.