Technical Data
TD534-0501002U
Instructions for the Installation,
Operation and Maintenance
of W-SLC-7.2
Effective January 2013
Overview
Introduction
Order instruction
Standard conformance
W-SLC is a contactor fuse combination withdrawable truck for use in indoor switchgear. It is rated at a continuous current rating of 400A
(with conductors) and 200A (with 355A fuses) and used up to 7.2kV 50Hz AC power systems. Incorporating Eaton’s fixed type SL series
of medium voltage vacuum contactors
.
W-SLC adds medium voltage current limiting fuses for short-circuit protection, to control medium
voltage equipment such as 3-phase motors, transformers, capacitor banks and is especially used in applications where frequent
operations are required.
IEC draw-out contactor
Contactor’s auxiliary contact
66
= 6 NO, 6 NC
Coil voltage
= 120/60 Hz
= 240/60 Hz
= 110/50 Hz
= 220/50 Hz
= 110 DC
= 220 DC
A
B
U
W
X
Y
Mechanical latch
(Coil voltage)
0
4
5
= None
= 110/50, 120/60 Hz
= 220/50, 240/60 Hz
IEC SL contactor
7.2 kV, 400 A
Coil drop-out time
= 30 ms
= 50 ms
= 130 ms
= 250 ms
= 330 ms
5
6
7
8
9
W-SLC 1 SLC014S 5
-
Y
66 5
= with fuses
= fuses replaced by conductors
1
0
Note: fuses are supplied by user
• IEC 60470-2000 High Voltage Alternative Current Contactors
and Contactor-Based Motor Starters
• IEC 62271-1 High-voltage switchgear and controlgear – Part 1:
Common specifications
Ambient conditions
a) Ambient temperature
Maxi
mu
m temperature: +40ºC
Minimum temperature: -15ºC
b) Ambient humidity
Average daily relative humidity:
≤
95%
Average monthly relative humidity:
≤
90%
Average daily vapor pressure:
≤
2.2 kPa
Average monthly vapor pressure:
≤
1.8 kPa
c) Altitude: not exceed 1000m
d) Ambient air is not significantly polluted by dust, smoke,
corrosive and/or flammable gases, vapor’s or salt.
Note:
please contact Eaton for requests exceeding the normal
ambient conditions shown above.