background image

6

Instruction Leaflet    

IL182403EN   July 2018   www.eaton.com

Factory Authorized Mechanism Enhancement (FAME)

 

SECTION 3:   INSPECTION & MAINTENANCE

m

 WARNING

DO NOT WORK ON A CIRCUIT BREAKER IN THE ‘CONNECT’ POSITION.

DO NOT WORK ON A CIRCUIT BREAKER WITH SECONDARY    

DISCONNECTS ENGAGED.

DO NOT WORK ON A CIRCUIT BREAKER WITH SPRINGS CHARGED OR 

CONTACTS CLOSED.

DO NOT DEFEAT ANY SAFETY INTERLOCKS.

DO NOT LEAVE MAINTENANCE TOOL IN THE SOCKET AFTER CHARGING 

THE CLOSING SPRINGS.

m

 WARNING

STAND AT LEAST ONE METER AWAY FROM THE CIRCUIT BREAKER WHEN 

TESTING FOR VACUUM INTEGRITY.

FAILURE TO FOLLOW ANY OF THESE INSTRUCTIONS MAY CAUSE 

EQUIPMENT FAILURE, RESULTING IN DEATH, SEVERE PERSONAL INJURY, 

EQUIPMENT DAMAGE AND/OR IMPROPER OPERATION. SEE SECTION 2 - 

SAFE PRACTICES FOR MORE INFORMATION.

3.1   INSPECTION FREQUENCY

The scheduled maintenance interval of a FAME upgraded power 

circuit breaker is 10 years or 10,000 operations, whichever comes 

first. However, it is recommended that the circuit breaker be 

inspected and cleaned on a regular interval based on the surrounding 

ambient conditions. Dust, contaminants and moisture can combine 

to create voltage tracking on the surfaces of insulating materials. An 

inspection schedule should be created based on the surrounding 

ambient conditions. Inspection schedules typically range from 1 to 5 

years, but may extend to more or less frequency depending on the 

cleanliness of the circuit breaker installation.
A vacuum integrity test should be performed as outlined in the OEM 

instruction booklet before the initial installation of a FAME upgraded 

circuit breaker and also anytime the circuit breaker is transported 

to a new circuit breaker compartment location. Additionally, it is 

recommended to inspect the circuit breaker every time it interrupts 

fault current.

otee:

N

The OEM instruction booklet contains specific inspection, maintenance 

and trouble shooting procedures. Refer to the table in the OEM instruction 

manual for maintenance and trouble-shooting. 

m

 WARNING

DO NOT FOLLOW THE LUBRICATION INSTRUCTIONS SHOWN IN THE OEM 

INSTRUCTION BOOKLET. THE CIRCUIT BREAKER MECHANISM SHOULD 

NEVER BE OILED OR RE-LUBRICATED IN ANY MANOR AFTER THE FAME 

UPGRADE IS PERFORMED. THE FAME WARRANTY WILL VOID IF ANY 

LUBRICATION IS PERFORMED ON THE CIRCUIT BREAKER THAT HAS THE 

FAME PROCESS APPLIED.

SECTION 4:   REPLACEMENT PARTS

4.1   GENERAL

The FAME upgrade is achieved with custom engineered sub-

assemblies available only from Eaton’s Power Breaker Center 

(PBC) and are not required for general maintenance or purchase 

for renewal parts. The FAME upgrade and repairs to the FAME 

mechanism should only be performed at Eaton’s PBC or one of the 

Power Breaker Reconditioning centers (PBRc).

m

 WARNING

DO NOT ATTEMPT TO REPAIR A FAME MECHANISM USING ANY OF THE 

RENEWAL PARTS LISTED IN THE OEM INSTRUCTION MANUAL.

In order to minimize production downtime, it is recommended that 

an adequate quantity of spare control parts be carried in stock. The 

quantity will vary from customer to customer, depending upon the 

service severity and continuity requirements. Each customer should 

develop their own level based on operating experience. However, 

when establishing a new operating record, it is a good practice to 

stock one set of control components for every six circuit breakers 

of the same control voltage. This quantity should be adjusted with 

time and frequency of operation of the circuit breakers. These 

components are not included in the FAME upgrade. Refer to the 

OEM instruction booklet for replacement control components.

Summary of Contents for VR Series

Page 1: ...July 2018 Instruction Leaflet IL182403EN Supersedes April 2017 Effective Factory Authorized Mechanism Enhancement FAME FAME Upgrade Shown...

Page 2: ...reaker design All possible contingencies which may arise during installation operation or maintenance and all details and variations of this equipment do not purport to be covered by these additional...

Page 3: ...ION 1 INTRODUCTION 4 1 1 VISUAL INSTRUCTION BOOKLET ESSENTIALS 4 1 2 QUICK RESPONSE CODE 4 1 3 ADDITIONAL LABEL INFORMATION 4 1 4 FAME CIRCUIT BREAKER ENHANCEMENTS 5 SECTION 2 SAFE PRACTICES 5 SECTION...

Page 4: ...1 1 VISUAL INSTRUCTION BOOKLET ESSENTIALS Eaton provides additional documentation designed to enhance the technical information provided in this instruction booklet for the VCP W and VR Series FAME c...

Page 5: ...quences m DANGER TO PROTECT THE PERSONNEL ASSOCIATED WITH INSTALLATION OPERATION AND MAINTENANCE OF THESE CIRCUIT BREAKERS THE FOLLOWING PRACTICES MUST BE FOLLOWED Only qualified persons as defined in...

Page 6: ...compartment location Additionally it is recommended to inspect the circuit breaker every time it interrupts fault current Note N The OEM instruction booklet contains specific inspection maintenance a...

Page 7: ...7 Instruction Leaflet IL182403EN July 2018 www eaton com Factory Authorized Mechanism Enhancement FAME...

Page 8: ...ulevard Cleveland OH 44122 United States Eaton com 2018 Eaton All Rights Reserved Printed in USA Publication No IL182403EN July 2018 Eaton is a registered trademark All trademarks are property of thei...

Reviews: