10
Instruction Booklet
IB131006EN
Effective March 2019
Instructions for installation,
operation, and maintenance of type
VCP-W vacuum circuit breakers
EATON
www.eaton.com
Table 5. (ANSI Standards
a
) type VCP-W (K = 1) vacuum circuit breaker through 15 kV rated symmetrical current basis (standard
ratings).
Identification
Rated values
a
Circuit
breaker
type
Nominal
voltage
class
Voltage
Insulation level
Current
Inter-
rupting
time
Permis-
sible
tripping
delay
Y
Max.
voltage
divided
by K
E/K
Current values
Max.
voltage
E
Voltage
range
factor
b
K
Withstand test
voltage
Continuous
current
at 60 Hz
Short
circuit
current
(at rated
max. kV)
c
I
Closing &
latching
capability
2.6 K
times
rated
short
Closing &
latching
capability
momentary
1.6 K
times rated
short
circuit
current
Power
frequency
(1 min.)
Impulse
kV
kV rms
kV rms
kV peak Amperes
kA rms
Ms
Seconds kV rms
kA peak
kA rms
50VCP-W 25
4.16
4.76
1.0
19
60
1200
2000
3000
25
3 or 5
2
4.76
65
39
50VCP-W 40
4.16
4.76
1.0
19
60
1200
2000
3000
40
3 or 5
2
4.76
104
62
50VCP-W 50
4.16
4.76
1.0
19
60
1200
2000
3000
50
3 or 5
2
4.76
130
78
50VCP-W 63
4.16
4.76
1.0
19
60
1200
2000
3000
63
3 or 5
2
4.76
164
98
75VCP-W 40
7.2
8.25
1.0
36
95
1200
2000
3000
40
3 or 5
2
11.5
104
62
75VCP-W 50
7.2
15
1.0
36
60
1200
2000
3000
50
3 or 5
2
11.5
130
78
150VCP-W 25 13.8
15
1.0
36
95
1200
2000
3000
25
3 or 5
2
15.0
65
39
150VCP-W 40 13.8
15
1.0
36
95
1200
2000
3000
40
3 or 5
2
15.0
104
62
150VCP-W 50 13.8
15
1.0
36
95
1200
2000
3000
50
3 or 5
2
15.0
130
78
150VCP-W 63 13.8
1.0
36
95
1200
2000
3000
63
3 or 5
2
15.0
164
98
a
All circuit breakers are tested to 60 Hz; however, they can also be applied at 50 Hz with no derating.
b
Consult the Consulting Application Guide CA08104001E sections 1 and 5 for further information.
c
Also 3-second short time current carrying capability.
Table 6. (ANSI Standards
a
) type VCP-WXC circuit breaker through 15 kV rated symmetrical current basis (standard ratings).
See Figure 23 for control schemes and diagram that apply to this breaker. This breaker differs from the standard breaker with the addition of a third motor cut-off switch and
addition of two wires.
Identification
Rated voltage
Circuit
breaker
type
Voltage
Insulation level
withstand test
Cont-
inuous
current
at
60 Hz
Short circuit current
Inter-
rupting
time
b
Max.
permis
sible
tripping
delay
Transient
recovery
voltage
(RRRV)
c
Capacitor switching ratings
Mech-
anical
endur-
ance
No-
load
oper-
ations
Max.
voltage
V
Voltage
range
factor
K
Sym
inter-
rupting
at V
(Isc)
% DC
comp-
onent
(Idc)
Asym.
inter-
rupting
(It)
Closing
&
latching
capa-
bility
Short-
time
current
for 3
sec.
General
purpose
Definite purpose
Power
freq-
uency
(1 min.)
Lighten-
ing
impulse
1.2x50us
Isolated
shunt
capaci-
tor
bank
current
Back to back capacitor
switching
capacitor
bank
current
Inrush
current
Inrush
freq-
uency
kV rms
kV rms
kV peak
A rms
kA rms
total
%
kA rms
kA
peak
kA rms
Cycles
Sec.
kV / µs
A rms
A rms
kA
peak
kHz
150 VCP-WXC
63
17.5
1
42
95
1200
2000
3000
63
61
61
61
83
83
83
175s
63
5
2
1.07
1.07
1.07
200,1600(9)
200,1600(9)
200,1600(9)
7.7
7.7
7.7
465
465
465
10,000
10,000
5,000
a
All circuit breakers are tested to 60 Hz; however, they can also be applied at 50 Hz with no derating.
b
Optional interrupting time of 3 cycles is available.
c
For higher RRRV contact Eaton for more information
.