Diagnostics/troubleshooting

The integrated racking controller programming has built-in 

diagnostics and error detection . If an error occurs, “E1” to “E9” will 

appear on the pendant display (see 

Figure 6

) . On the back of the 

pendant there is a label that explains what the error is and what to 

do if the error occurs (see 

Figure 9

) .

Figure 6. MR2 Error code display.

Figure 7. MR2 O/C error code display.

Figure 8. MR2 O/C error code display with out  

connect/disconnect.

Figure 9. MR2 error code display.

Figure 10. MR2 O/C error code display.

E1: Motor overcurrent

Condition when motor current is in excess of allowed value . Multiple 

causes could create this condition . E1 error codes may occur if 

system is operated on temporary generator power . Operator should 

shut off power to the VC-W MR2 controller by tripping the 15 A 

circuit breaker (see 

Figure 11

) in the LV compartment and manually 

rack out the MV device . The operator should inspect the MV device, 

levering system subassembly, and controller card for obvious 

damage or abnormal conditions . If no obvious issues are found, 

reinstall the MV device  .

E2: Open motor circuit

Can occur when the motor thermal switch opens, possibly caused 

by an excessive duty cycle (more than 10 consecutive operations in 

quick succession without stopping) . Once the thermal switch closes 

(motor cools down), the controller can be reset by pressing the 

disconnect switch .

An open motor circuit as shown (

Figure 1

 and 

2

) will also cause this 

error .  Use troubleshooting as shown with

 

Figure 1

 and 

2

 .

Summary of Contents for VC-W MR2

Page 1: ...Open permissive 9 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking Description Page E6 Communication error 9 E7 No MV device 9 E8 Firmware compatibi...

Page 2: ...2 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com...

Page 3: ...source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PA...

Page 4: ...SC 29649 All possible contingencies which may arise during installation operation or maintenance and all details and variations of this equipment are not encompassed by these instructions If further i...

Page 5: ...ive interlocks wired for every breaker cell with integrated racking and one for every auxiliary cell with integrated racking Breaker cell specific interlocks 1 Normally closed mechanism operated compa...

Page 6: ...pass E5 error circuit CAUTION by jumpering terminals 51 to 54 you have defeated the inter lock circuit For troubleshooting move the black mo tor lead on terminal 47 to terminal 44 to bypass E2 error c...

Page 7: ...the auxiliary pan assembly This lock prohibits an operator from manually inserting a crank into the Lev in assembly and manually racking the breaker or auxiliary device as specified in the switchgear...

Page 8: ...hen motor current is in excess of allowed value Multiple causes could create this condition E1 error codes may occur if system is operated on temporary generator power Operator should shut off power t...

Page 9: ...ibility error This state results from the pendant and controller card not having compatible firmware Contact your Eaton representative to have the firmware updated E9 No test MR2 open close only This...

Page 10: ...Disconnect buttons can be used to scroll up and down 01 to 99 until the desired address number is reached While scrolling the Connect LED will continue to flash to let the user know that the address...

Page 11: ...device from a distance of up to 30 ft 9 14 m from the equipment with a Cat 5 cable typically there will be an RJ 45 jack located on the front panel of the switchgear see Figure 14 The MV device can b...

Page 12: ...cking device via a SCADA system or multiple Modbus interface communication systems These systems can be wired to a central control room or to a remote panel located a safe distance away from the equip...

Page 13: ...ontrol power to breaker a At this time the breaker open and close operations can be tested electrically b To proceed further and rack the breaker to the connected position the breaker must be open 1 A...

Page 14: ...ator should then open the breaker c After the breaker is open the error can be cleared by pressing the disconnect button 8 Once the error is cleared the operator can rack the breaker to the test or di...

Page 15: ...15 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com Notes...

Page 16: ...16 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com...

Page 17: ...17 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com...

Page 18: ...n USA Publication No IB022010EN TBG001320 July 2019 Eaton is a registered trademark All other trademarks are property of their respective owners Instructions for installation operation and maintenance...

Reviews: