![Eaton URTDII Instruction Leaflet Download Page 6](http://html1.mh-extra.com/html/eaton/urtdii/urtdii_instruction-leaflet_3854258006.webp)
Wire
Shield/Drain
USE TAPE TO INSULATE
CABLE'S SHIELD WIRE AT THIS END!
Terminals
Motor
DO NOT CONNECT
Terminals
Motor
USE TAPE TO INSULATE
CABLE'S SHIELD WIRE AT THIS END!
DO NOT CONNECT
Wire
Shield/Drain
Notes:
Connect cable shield at URDTII terminals only. Cut shield short at motor end
1.
and use shrink tubing or electrical tape to insulate.
RTDs must not be grounded at the motor and no common connections
2.
between individual RTDs should be made at the motor.
Figure 5, Wiring to URTDII
6
IL02602013E
Universal Resistance Temperature
November 2010
Detector (RTD) Module II
IL02602013E - November 2010 - www.eaton.com