USE TAPE TO INSULATE
DO NOT CONNECT CABLE'S SHIELD WIRE AT THIS END!
Figure 4. RTD Wiring (Three-Lead Type)
otee:
N
Each shielded cable conductor must be connected on the URTDII as shown.
1.
Use of three-lead RTDs is recommended.
2.
RTDs must not be grounded at the motor, and no common connections between RTDs
3.
should be made at the motor.
A suitable earth ground should be connected to J10B-4, J10B-11, J-10B-18, J2-4, J2-11, or
4.
J2-18. It is recommended that a ground connection is made to both sides of the unit.
5
Universal Resistance Temperature IL02602013E
Detector (RTD) Module II
November 2010