RMU HMH 36-02 FUSE+LOAD ISOLATOR COMPOUND

Load disconnector maneuvers

OPERATIONAL INSTRUCTIONS

Assembling the closing spring:

Place the assembly lever to spring assembly housing as shown in 
the figure and rotate it in arrow direction.
Ensure that it makes the assembly sound when assembling the 
closing spring. 
If there is a 

spring assembly engine in the cell,

 the spring shall 

automatically be assembled when the low voltage fuses are off.

After the assembly of the closing spring:

Earthing disconnector is on, Closing spring is assembled (load 
disconnector is no)

Turning the load disconnector off:

To turn the load disconnector off, press the off button.
Or plug the remote control given with the cell group into the 
remote socket and press the off button.

Position of load disconnector after turning off:

Earthing disconnector is no, opening spring is assembled Load 
disconnector is off

I

I

K

A

TOPRAK

FLBSG  36

S

İGORTALI RMU

www.ulusoyelektrik.com.tr

D

İKKAT

BU HÜCRE G

İRİŞ HÜCRESİ OLARAK

KULLANILIYOR 

İSE,BİRÖNCEKİ

MERKEZDEN ENERJ

İSİNİ KESMEDEN

TOPRAK AYIRICISINI

KAPATMAYINIZ.

YÜK AYIRICISI

YAY KURMA

TOPRAK AYIRICISI

KAPAMA

AÇMA

İŞLEM SIRASI

0

I

0

I

36kV / 200A / 16kA

Ud/Up :70/170kV IP3X

IEC :62271-200

I

I

K

A

TOPRAK

FLBSG  36

S

İGORTALI RMU

www.ulusoyelektrik.com.tr

D

İKKAT

BU HÜCRE G

İRİŞ HÜCRESİ OLARAK

KULLANILIYOR 

İSE,BİRÖNCEKİ

MERKEZDEN ENERJ

İSİNİ KESMEDEN

TOPRAK AYIRICISINI

KAPATMAYINIZ.

YÜK AYIRICISI

YAY KURMA

TOPRAK AYIRICISI

KAPAMA

AÇMA

İŞLEM SIRASI

0

I

0

I

36kV / 200A / 16kA

Ud/Up :70/170kV IP3X

IEC :62271-200

I

I

K

A

TOPRAK

FLBSG  36

S

İGORTALI RMU

www.ulusoyelektrik.com.tr

D

İKKAT

BU HÜCRE G

İRİŞ HÜCRESİ OLARAK

KULLANILIYOR 

İSE,BİRÖNCEKİ

MERKEZDEN ENERJ

İSİNİ KESMEDEN

TOPRAK AYIRICISINI

KAPATMAYINIZ.

YÜK AYIRICISI

YAY KURMA

TOPRAK AYIRICISI

KAPAMA

AÇMA

İŞLEM SIRASI

0

I

0

I

36kV / 200A / 16kA

Ud/Up :70/170kV IP3X

IEC :62271-200

Kapama

butonu

I

I

K

A

TOPRAK

FLBSG  36

S

İGORTALI RMU

www.ulusoyelektrik.com.tr

D

İKKAT

BU HÜCRE G

İRİŞ HÜCRESİ OLARAK

KULLANILIYOR 

İSE,BİRÖNCEKİ

MERKEZDEN ENERJ

İSİNİ KESMEDEN

TOPRAK AYIRICISINI

KAPATMAYINIZ.

YÜK AYIRICISI

YAY KURMA

TOPRAK AYIRICISI

KAPAMA

AÇMA

İŞLEM SIRASI

0

I

0

I

36kV / 200A / 16kA

Ud/Up :70/170kV IP3X

IEC :62271-200

Summary of Contents for Ulusoy URING36 F-SF6

Page 1: ...Ulusoy URING36 F SF6 Insulated Transformer Protection RMU Switchgear with Fuse and LBS User Manual www eaton com...

Page 2: ...S AND CHECKS BEFORE POWERING USE TEST TO BE PERFORMED BEFORE POWERING OPERATIONAL INSTRUCTIONS OPERATIONAL INSTRUCTIONS EARTHING DISCONNECTOR MANEUVERS OPERATIONAL INSTRUCTIONS LOAD DISCONNECTOR MANEU...

Page 3: ...CONTROL SOCKET 1 LOW VOLTAGE BOARD 2 MECHANISM SECTION 3 MEDIUM FUSE HOUSINGS 4 CABLE HEAD CONNECTION TERMINAL 5 CABLE CONNECTION CLAMPS 6 BAR CONNECTION TERMINALS SINGLE LINE SCHEME 6 3 1 4 5 7 9 8 2...

Page 4: ...ed Fuse selection tables according to manufacturers are below Select the fuse amperages from the lists below according to the power of the transformer you will use and according to the fuse brand you...

Page 5: ...N ACCORDING TO THE PLASTIC PIECE IF THE WARNING LIGHTS ON THE SIGNAL LIGHT BOX ARE ON RESET THE SITUATION BY PRESSING DELETE BUTTON AND COMPLETE THE PROCEDURE CLOSE THE CELL DOOR AFTER FINISHING THE P...

Page 6: ...are foreign objects in the switchgear Check the connections of the cells Check if all fuses are placed correctly in all phases Check if the front cover is placed correctly If the front cover is not fi...

Page 7: ...r and earthing disconnector a few times Use test to be performed before powering RMU 36 02 cells I I K A TOPRAK FLBSG 36 S GORTALI RMU www ulusoyelektrik com tr D KKAT BU H CREG R H CRES OLARAK KULLAN...

Page 8: ...YAY KURMA TOPRAK AYIRICISI KAPAMA A MA LEM SIRASI TOPRAK AYIRICISINI A YAYKUR H CRE KAP ISINI KAPA T 0 Y K AYIRICISINI KAPA T Y K AYIRICISINI A H CREDE ISLEM VAR MI HAYIR EVET TOPRAK AYIRICISINI KAPA...

Page 9: ...URMA TOPRAK AYIRICISI KAPAMA A MA LEM SIRASI 0 I 0 I 36kV 200A 16kA Ud Up 70 170kV IP3X IEC 62271 200 I I K A TOPRAK FLBSG 36 S GORTALI RMU www ulusoyelektrik com tr D KKAT BU H CR E G R H CR ES OLARA...

Page 10: ...ANILIYOR SE B R NC EK MERKEZDEN ENERJ S N KESMEDEN TOPRAKAYIRICISINI KAPATMAYINIZ Y K AYIRICISI YAY KURMA TOPRAK AYIRICISI KAPAMA A MA LEM SIRASI 0 I 0 I 36kV 200A 16kA Ud Up 70 170kV IP3X IEC 62271 2...

Page 11: ...OPRAKAYIRICISINI KAPATMAYINIZ Y K AYIRICISI YAY KURMA TOPRAK AYIRICISI KAPAMA A MA LEM SIRASI 0 I 0 I 36kV 200A 16kA Ud Up 70 170kV IP3X IEC 62271 200 A ma butonu I I K A TOPRAK FLBSG 36 S GORTALI RMU...

Page 12: ...ector is off To replace a faulty voltage indicator Open the front cover of low voltage assembly board of the cell Remove the faulty indicator by dismantling its latches and replace it with a new one T...

Page 13: ...the earthing disconnector is on Load disconnector cannot be operated electrically Check if low voltage connections are done Check if low voltage fuses are off Check if the earthing blade is completely...

Page 14: ...n is to improve the quality of life and the environment through the use of power management technologies and services We provide sustainable solutions that help our customers effectively manage electr...

Reviews: