Ulusoy URING
36
F - SF
6
Insulated
Transformer Protection RMU Switchgear with Fuse and LBS User Manual
www.
eaton
.com
Page 1: ...Ulusoy URING36 F SF6 Insulated Transformer Protection RMU Switchgear with Fuse and LBS User Manual www eaton com...
Page 2: ...S AND CHECKS BEFORE POWERING USE TEST TO BE PERFORMED BEFORE POWERING OPERATIONAL INSTRUCTIONS OPERATIONAL INSTRUCTIONS EARTHING DISCONNECTOR MANEUVERS OPERATIONAL INSTRUCTIONS LOAD DISCONNECTOR MANEU...
Page 3: ...CONTROL SOCKET 1 LOW VOLTAGE BOARD 2 MECHANISM SECTION 3 MEDIUM FUSE HOUSINGS 4 CABLE HEAD CONNECTION TERMINAL 5 CABLE CONNECTION CLAMPS 6 BAR CONNECTION TERMINALS SINGLE LINE SCHEME 6 3 1 4 5 7 9 8 2...
Page 4: ...ed Fuse selection tables according to manufacturers are below Select the fuse amperages from the lists below according to the power of the transformer you will use and according to the fuse brand you...
Page 5: ...N ACCORDING TO THE PLASTIC PIECE IF THE WARNING LIGHTS ON THE SIGNAL LIGHT BOX ARE ON RESET THE SITUATION BY PRESSING DELETE BUTTON AND COMPLETE THE PROCEDURE CLOSE THE CELL DOOR AFTER FINISHING THE P...
Page 6: ...are foreign objects in the switchgear Check the connections of the cells Check if all fuses are placed correctly in all phases Check if the front cover is placed correctly If the front cover is not fi...
Page 7: ...r and earthing disconnector a few times Use test to be performed before powering RMU 36 02 cells I I K A TOPRAK FLBSG 36 S GORTALI RMU www ulusoyelektrik com tr D KKAT BU H CREG R H CRES OLARAK KULLAN...
Page 8: ...YAY KURMA TOPRAK AYIRICISI KAPAMA A MA LEM SIRASI TOPRAK AYIRICISINI A YAYKUR H CRE KAP ISINI KAPA T 0 Y K AYIRICISINI KAPA T Y K AYIRICISINI A H CREDE ISLEM VAR MI HAYIR EVET TOPRAK AYIRICISINI KAPA...
Page 9: ...URMA TOPRAK AYIRICISI KAPAMA A MA LEM SIRASI 0 I 0 I 36kV 200A 16kA Ud Up 70 170kV IP3X IEC 62271 200 I I K A TOPRAK FLBSG 36 S GORTALI RMU www ulusoyelektrik com tr D KKAT BU H CR E G R H CR ES OLARA...
Page 10: ...ANILIYOR SE B R NC EK MERKEZDEN ENERJ S N KESMEDEN TOPRAKAYIRICISINI KAPATMAYINIZ Y K AYIRICISI YAY KURMA TOPRAK AYIRICISI KAPAMA A MA LEM SIRASI 0 I 0 I 36kV 200A 16kA Ud Up 70 170kV IP3X IEC 62271 2...
Page 11: ...OPRAKAYIRICISINI KAPATMAYINIZ Y K AYIRICISI YAY KURMA TOPRAK AYIRICISI KAPAMA A MA LEM SIRASI 0 I 0 I 36kV 200A 16kA Ud Up 70 170kV IP3X IEC 62271 200 A ma butonu I I K A TOPRAK FLBSG 36 S GORTALI RMU...
Page 12: ...ector is off To replace a faulty voltage indicator Open the front cover of low voltage assembly board of the cell Remove the faulty indicator by dismantling its latches and replace it with a new one T...
Page 13: ...the earthing disconnector is on Load disconnector cannot be operated electrically Check if low voltage connections are done Check if low voltage fuses are off Check if the earthing blade is completely...
Page 14: ...n is to improve the quality of life and the environment through the use of power management technologies and services We provide sustainable solutions that help our customers effectively manage electr...