Cable Entrance
Auxiliary supply cable entrance is located
on side part of the LV Panel.
You can connect the auxiliary supply cable to the first or the last switchgear of the set.
Follow the wiring scheme of switchgear to know how to connect Aux. supply circuit.
Supplying Auxiliary Circuit
10
Ulusoy HMH24-02 Transformer Protection Switchgear (LBS Compound Fuse)
September 2020 www.eaton.com
Connect the cable to L1 (inner) phase. Torque with
50Nm. Put the bottom sheet and close the cable
clamps. After that apply the same prosedure to L2
and L3.
Prepare the cable termination.