Technical Data
Effective August 2018
ote:
n
(a) Tones approved under the Construction Products Regulation for Fire Alarm Applications, are shown in the column marked EN54-3.
ote:
n
(b) EN54-3 measurements shown reflect minimum expected SPL readings at Maximum Volume at the Loudest Point around the EN54-3 defined sounder axis.
ote:
n
(c) Detailed EN54-3 polar SPL measurements are available in the Product Manual M96-003.
ote:
n
(e) All measurements taken at 20
°
C operating temperature.
Squashni Micro
Squashni Micro/E
Low output setting
(Switch 4=0)
High output setting
(Switch 4=1)
Low output setting
(Switch 4=0)
High output setting
(Switch 4=1)
Tone
mA
*24Vdc
on Axis
dB(A)
EN54-3
28Vdc
see
notes
dB(A)
Tone SW
setting
(1) (2)
mA
*24Vdc
on
Axis
dB(A)
EN54-3
28Vdc
see
notes
dB(A)
mA
*24Vdc
on Axis
dB(A)
EN54-3
28Vdc
see
notes
dB(A)
Tone SW
setting
(1) (2)
mA
*24Vdc
on Axis
dB(A)
EN54-3
28Vdc
see
notes
dB(A)
3
Sweep
800 ~ 970Hz
1Hz (1/s)
5.5
90
93
1 1
15
97
99
7
Slow Whoop 300 ~ 1200Hz 3s sweep, 0.5s
silence, repeat
4
85
85
1 1
8
90
93
8
Sweep (DIN) 1200 ~ 500Hz 1Hz
4
85
89
0 1
8
90
91
30
Alternating
510 & 610Hz
2Hz
(250ms-250ms)
3
88
88
0 1
9
95
97
4
85
86
0 0
8
90
92
35
Continuous
510Hz
Steady
3
88
88
0 0
9
95
96
4
85
89
1 0
8
90
93
36
Intermittent
510Hz
1Hz (500ms On
/ 500ms Off)
3
89
89
1 0
10
95
96
(2nd tone on SQM sounder is intermittent, Tone 36)