6
System Parallel Module
3 .2 .1 Environmental and Installation Considerations
The UPS system installation, including the SPM, must meet the following guidelines:
•
The system must be installed on a level floor or stiff wall which is suitable for computer or electronic
equipment.
•
Suitable for mounting on concrete or other non-combustible surfaces only.
•
The system must be installed in a temperature and humidity controlled indoor.
Failure to follow guidelines may void your warranty.
The SPM operating environment must meet the weight requirements shown in Table 3-1 and the size
requirements shown in Figure 3-1 through Figure 3-2. Dimensions are in millimetres (inches).
No special rear clearances required for the SPM, other clearances around the SPM cabinet can follow
the UPS.
The basic environmental requirements for operation of the UPS and Accessories are:
• Ambient Temperature Range: 5–40°C (41–104°F)
• Recommended Operating Range: 20–25°C (68–77°F)
• Maximum Relative Humidity: 95%, noncondensing
Table 3-1 . SPm Cabinet Weights
Eaton 1+1 120kVA SPM
348(767)
270(595)
33.8 (77.4)/wheel (total 8 wheels)
Eaton 2+1 120kVA SPM
Eaton 3+1 120kVA SPM
Eaton 1+1 200kVA SPM
363.5(801)
285.5(629)
35.6 (78.4)/wheel (total 8 wheels)
Eaton 2+1 200kVA SPM
Eaton 3+1 200kVA SPM
model
Weight kg (lb)
Shipping
Installed
Point loading
Table 3-2 . SPm Cabinet Clearances
from Top of Cabinet
No requirement
from front of Cabinet
900 mm (36") working space
from Back of Cabinet
No requirement
from right Side of Cabinet
No requirement
from left Side of Cabinet
No requirement