Electrical Installation
65
02/11 MN05006002Z-EN
Ensure that the PCB is pointing in the correct direction.
The direction of the arrow defines the arrangement of the
SmartWire-DT slaves. The SmartWire-DT gateway is to the
left of the IN code.
Direct connection of SmartWire-DT round cable
Figure 18:
Direct connection with a cable gland
X
Jacket and insulate the SmartWire-DT round cable to a
suitable length.
X
Fit the individual wires with insulated ferrules with plastic
collars in accordance with DIN 46228, Part 4, of suitable
cross-section and a length of at least 8 mm.
X
Introduce the SmartWire-DT round cable coming from the
gateway side through the fitted cable gland and into the
surface mounting enclosure.
X
If further SmartWire-DT slaves follow this surface
mounting enclosure, introduce the second SmartWire-DT
round cable fitted with wire-end sleeves through another
cable gland and into the surface mounting enclosure.
X
Then connect the wires to the PCB.
1
3
2
2
IN
V-M20
i
Warning!
Ensure the secure seating of the cable and safe operation
by using the integrated strain relief for the cable gland.