Instruction Bulletin
Instructions for Installation,
Page 5
Effective: July 2016
Operation and Maintenance of the
SL800 Classic 7.2 Kilovolt, 720 Amp. Vacuum Contactor
For more information visit:
www.eaton.com
IB48082
Fig. 3 Coil Control Board with Dip Switch
TABLE IIIb. CONTROL BOARD DROPOUT SETTINGS
Delay Setting
SW4
SW5
SW6
50 ms
On
Off
Off
130 ms
Off
On
Off
250 ms
On
On
Off
330 ms
Off
Off
On
The control board provides the economizing function
for the main coil circuit. The L63 interlock used in
the economizing circuit on the SJA800A contactor is
therefore not needed in this design. It has been
removed from the SL800 Classic contactor.
WIRING
Refer to Figure 4 for standard control wiring for
magnetically held contactors. To close the contactor,
apply power to terminals 1 and 2 on the control
board. Power must be maintained to terminals 1 and
2 to keep the contactor in the closed position. The
closing coil is connected to terminals 5 and 6.
Fig. 4 Connections for Magnetically Held Contactor
RENEWAL AND REPLACEMENT PARTS
•
SL800 Classic VI Assemblies, set of three -
54A1307G27
•
Control Board
- 54A1307G24
•
Contactor Coil - 54A1307G18