27
External Battery Cabinets
Chapter 7 Product Specifications
The following sections detail the battery specifications, battery runtimes, and the environmental and safety
specifications for the EBC.
This section provides the following specifications:
•
Model Numbers
•
Battery specifications
•
Battery runtimes
•
Environmental and safety specifications
7 .1
Specifications
operating Temperature
①
5°C – 40°C
Storage Temperature
①
-25°C to 55°C
Transit temperature
①
-25°C to 60°C
humidity
5 % to 95 % maximum noncondensing
Enclosure Class per IEC 60529
IP21 with door opened
rohS/WEEE
Required
operating Altitude
②
Maximum 1000m at 30°C without derating
7 .1 .1 Environmental
specifications
①
The recommended operational, storage and transit temperature with CSB and C&D batteries is
generally max. 25°C. Please refer to the battery manufacturer’s recommendations for accurate
temperatures.
②
Altitude-thermal de-rating as per EN62040-3:2011.
Battery type
VRLA, 12 VDC
Battery quantity
93PM 30-50 kW units:
1) 36 blocks, 216 cells per battery string, 2V per cell.
2) 40 Blocks, 240 cells per battery string.
93PM 80-200 kW units:
1) 36 blocks, 216 cells per battery string, or
2) 40 blocks, 240 cells per battery string, 2V per cell.
93E 80-200 kVA units:
1) 36 blocks, 216 cells per battery string, or
2) 38 blocks, 228 cells per battery string, or
3) 40 blocks, 240 cells per battery string, 2V per cell.
note! Battery strings with different battery quantity and
voltage must not be connected in parallel!
Battery Voltage
432 V (36 blocks) or 456V (38 blocks) or 480 V (40 blocks)
7 .1 .2 Battery
specifications