Mounting
The unit is provided with four 6mm diameter fixing holes for wall mounting.
The mounting holes can be accessed by undoing the four screws on the front cover and
removing it.
The unit should be installed in a dry ventilated location, where ambient temperature and
humidity are within the operating temperature of the unit.
The unit has ventilation slots on its sides to allow convection cooling and under no
circumstances should these be blocked.
Recommended minimum clearance around the unit is 100mm each side of the unit and 50mm
above and below the unit if trunking with a depth greater than 50mm is used.
Connecting Mains Supply
This unit requires a nominal 230V single phase supply (Live, Neutral and Earth) with 1A capability.
A separate isolator and secure mains earth are required.
All wiring should be completed in accordance with local wring regulations.
The unit is supplied with a knockout for mains cable entry. An appropriate cable gland should be
fitted to the knockout hole provided to protect the mains cable from damage.
Ensure all mains connections are fully tightened and lock-washers used where supplied.
DMX Connections
The SCD24 has 24 channels
of DMX that can be
configured via the iLight
programming software.
Connections are made via the
4-way 2 part terminal block.
Connections are:
Function
Alarm
(N/A)
0V
DMX+
DMX-