![Eaton RT 1250VA User Manual Download Page 31](http://html1.mh-extra.com/html/eaton/rt-1250va/rt-1250va_user-manual_527297031.webp)
29
7.3 EMC standard/Safety standard
◆
Our product are manufactured according to the following EMC international
grade standard and has passed the CE authentication
:
7.4 Product Performance
7.4.1 Electric performance
Model
RT
1250VA
RT
1250VA(H)
RT
2000VA
RT
2000VA(H)
RT
3000VA
RT
3000VA(H)
Rated capacity
800W/1000VA
1600W/2000VA
2400W/3000VA
input
input
Single phase and earthing
Voltage range
115±5VAC-295±5VAC
Frequency
45Hz-55Hz@50Hz/55Hz-65Hz@50Hz
Power factor
≥0.98
ECO range
setting rated output voltage ±20VAC
Bypass range
186VAC-252VAC
output
Output style
Single phase and earthing
Rated voltage
208/220/230/240VAC
Power factor
0.8
Voltage precision
±2%
Output
Fre-
quency
Line mode
1、When input frequency is in the range,the output frequency is
the same as that of input.
2、When input frequency is out of the range,the output frequency
of output is (50/60±0.2)Hz
Battery
mode
(50/60±0.2)Hz
Crest ratio
3:1
Transfer time
mains←→battery =0ms
mains←→bypass <4ms
Overload
capacity
Battery
mode
108%±5%<load≤150%±5% >30s cut off output and warn,
150%±5%<load<200%±5% > 300ms cut off output and warn
Line mode
108%±5%<load≤150%±5% > 30s transfer to bypass and warn
150%±5%<load<200%±5% >300ms transfer to bypass and warn
efficiency
mains
Full load≥87%
Full load≥88%
battery
Full load≥85%
ECO
Full load≥94%
EMC standard number
Safety standard number
IEC62040-2
IEC62040-1
IEC61000-4-2
GB4943-2005
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5