Impulse input:
The impulse input counts the impulses at its 2 separate S0 interfaces and forwards the readings to
a Room Manager with Energy function.
It features 2 separate channels independent from each other which can be configured by means of
the MRF.
Activate sending: Here you can select whether or not the value counted for this channel should be
transmitted.
Send all cyclically: Here the cycle time for transmission can be set between 10 minutes and 1 hour.
The impulse input has two 32 bit counters (1 for each channel) and counts all impulses at its S0
inputs in absolute figures until they are reset or until they are supposed to run over.
The maximum counting frequency of the impulses is defined in the Standard for S0 interfaces, it is
16 Hz.
All the other settings, such as the unit of the variable to be measured or the counting constant of
the connected counter can be done at the Room Manager, in the Settings window for the Energy
input.
Room Manager with Energy function – Input with Impulse input
Remote Control with Display
The Remote Control with Display is a 12-channel remote control with LCD display and a timer
function for up to 3 timers.
Summary of Contents for RF System 2.42
Page 1: ...Eaton RF System 2 42 Manual...
Page 123: ...123 Eaton RF System 2015 Eaton Electrical Group State Syntax of RM to user...
Page 193: ...193 Eaton RF System 2015 Eaton Electrical Group...
Page 200: ...200 Eaton RF System Help 2015 Eaton Electrical Group 7 And assign the function Blinking to it...
Page 223: ...223 Eaton RF System 2015 Eaton Electrical Group Group settings analogue actuator...
Page 224: ...224 Eaton RF System Help 2015 Eaton Electrical Group Group settings heating actuator...
Page 225: ...225 Eaton RF System 2015 Eaton Electrical Group Group settings binary input battery supplied...
Page 227: ...227 Eaton RF System 2015 Eaton Electrical Group Group settings Temperature input...