1.6 Selection criteria
Select RAMO5 or RASP5
③
according to supply voltage U
LN
of the supply
system
①
and the rated operational current of the assigned motor
②
.
The circuit type (
Δ
/
) of the motor must be selected according to the
supply voltage
①
. The RASP’s rated output current I
e
from the RASP5 must
be greater than or equal to the rated motor current. For RAMO5, current
monitoring must be set to the rated motor current.
Figure 7:
Selection criteria
When selecting the drive, the following criteria must be known:
•
Type of motor (three-phase asynchronous motor)
•
Grid voltage = rated voltage of the motor (e. g. 3~ 400 V),
•
Rated motor current (recommended value, dependent on the circuit type
and the supply power supply)
•
Load Torque,
•
Starting torque,
•
Ambient temperature range.
ATTENTION
Do not connect or disconnect power connectors (mains, motor)
while RAMO5 and RASP5 are operational.
230 / 400 V ∆ /
4.6 / 2.6
1.1
0.81
ϕ
cos
kW
min
-1
1430
50 Hz
A
②
①
U, I, f
③
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...