5 RAMO5 Motor starter
5.7 Configure special settings
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
127
5.7 Configure special settings
5.7.1 Configure set rated motor current (P1-08)
Before commissioning the RAMO5 motor control unit, the current monitor-
ing function must be set to the rated motor current.
To set parameter P1-08, the screw plug must be opened.
Figure 87: Set rated motor current
The parameterization can be via:
•
App,
•
Keypad,
•
“drivesConnect” software.
Table 22:
Parameter P1-08
ATTENTION
Parameter P1-08 can only be changed if the key switch is in the
OFF/RESET position.
Switching during operation may cause an accidental motor start.
Parameter
Description
Unit
Value range
P1-08
Motor nominal current
A
0.3 - 6.6
1410 mi n
230/400 V
3.2/1.9 A
50 Hz
-1
1,1KW
cos ϕ 0.79
P1-08