Technical Data
TD150030EN
Effective June 2019
PXMP display quickstart guide
Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2019 Eaton
All Rights Reserved
Printed in USA
Publication No. TD150030EN / TBG001463
June 2019
Eaton is a registered trademark.
All other trademarks are property of their
respective owners.
Figure 3. Mounting the PXMP display.
Connections
To use the PXMP display, provide 24 Vdc and connect the communi-
cation cable between the display and the PXMP meter base.
The Eaton PSG60E is an appropriate 24 Vdc power supply for both
the PXMP-MB meter base and PXMP display. The display’s plug-in
terminals provide connections for +24, GND and Common (0).
Figure 4. PXMP-DISP-6-XV.
Included with the PXMP display is a communications cable to con-
nect DB9 Com 2 of the display to 4-terminal Com 2 of the PXMP
meter base.
For best results, use the default communication settings for the
PXMP-MB and PXMP display (115.2 kbps, 1 start bit, 1 stop bit, no
parity).
otee:
N
By default, the PXMP display is preset for a PXMP meter base slave
address of “01”. To accommodate a different slave address, the User MUST
change the PXMP display’s “Modbus ID”. This setting can be found under
Settings > Meter ID.
Figure 6. Changing the Modbus ID.
5
4
3
2
1
9
8
7
6
Eaton P/N 67A2124HXX
YY-MM-DD
2.0"
PIN 2
PIN 3
RED
WHITE
BLACK
PIN 1
PIN 4
BARE
72.0"
PIN 1
PHOENIX CONN.
TERMINATION
PIN 3
PIN 5
PIN 7
RED
BLACK
WHITE
DB9 SHELL
DB9 TERMINATION
H12 (XV)
SHIELD WIRE TERMINATED to
67A2124H12
PSG60E
Power supply
connections
(-)
(+)
N
L
(-)
(+)
Display 24 VDC
control power
terminal
Figure 5. Power and COM port communications for the PXMP touch screen display.