background image

Technical Data 

TD150030EN

Effective June 2019

PXMP display quickstart guide

Eaton 

Electrical Sector

1000 Eaton Boulevard

Cleveland, OH 44122

United States

877-ETN-CARE (877-386-2273)

Eaton.com

© 2019 Eaton

All Rights Reserved

Printed in USA

Publication No. TD150030EN / TBG001463

June 2019

Eaton is a registered trademark. 

All other trademarks are property of their 

respective owners.

Figure 3. Mounting the PXMP display.

Connections

To use the PXMP display, provide 24 Vdc and connect the communi-

cation cable between the display and the PXMP meter base.
The Eaton PSG60E is an appropriate 24 Vdc power supply for both 

the PXMP-MB meter base and PXMP display.  The display’s plug-in 

terminals provide connections for +24, GND and Common (0).

Figure 4. PXMP-DISP-6-XV.

Included with the PXMP display is a communications cable to con-

nect DB9 Com 2 of the display to 4-terminal Com 2 of the PXMP 

meter base.
For best results, use the default communication settings for the  

PXMP-MB and PXMP display (115.2 kbps, 1 start bit, 1 stop bit, no 

parity).

otee:

N

By default, the PXMP display is preset for a PXMP meter base slave 

address of “01”.  To accommodate a different slave address, the User MUST 

change the PXMP display’s “Modbus ID”.  This setting can be found under 

Settings > Meter ID.

Figure 6. Changing the Modbus ID.

5

4

3

2

1

9

8

7

6

Eaton P/N 67A2124HXX

YY-MM-DD

2.0"

PIN 2
PIN 3

RED
WHITE
BLACK

PIN 1

PIN 4

BARE

72.0"

PIN 1

PHOENIX CONN.

TERMINATION

PIN 3
PIN 5
PIN 7

RED
BLACK
WHITE

DB9 SHELL

DB9 TERMINATION

H12 (XV)

SHIELD WIRE TERMINATED to

67A2124H12

PSG60E 
Power supply
connections

(-)

(+)

N

L

(-)

(+)

Display 24 VDC 
control power
terminal 

Figure 5. Power and COM port communications for the PXMP touch screen display.