5. DNP3 Ethernet Communication Setup Configuration Utility 

PXM 4/6/8K DNP3 Ethernet Communications User Manual

   MN150005EN   January 2017   www.eaton.com

The User can set three parameters:
1.  DNP Master Address

It is the address of DNP master with which the PXM 

meter shall exchange DNP3 data.  This address shall be 

validated by PXM meter and responses shall be sent 

ONLY if a request is sent by the DNP master with this 

address.  This address shall be used in DNP3 source 

field in DNP frames from master to slave. 

2.  PXM Meter Address

This is the DNP3 address with which the DNP3 mas-

ter device shall identify the specific PXM meter in the 

DNP network.  This address shall be used in the DNP3 

destination field in DNP frames from master to slave.  

The PXM meter shall match the destination address in 

the received frame and the User assigned PXM meter 

address.  If a match is found, then the frame shall be 

processed further.

3.  User Assigned ID/Code

The User can assign a name to the PXM meter for 

identification.  This helps in easy identification of the 

PXM meter location by the user instead of remember-

ing the meter by the DNP3 address.

otee:

N

PXM DNP3 implementation uses port 20,000 for its 

communication.  This port is not configurable and is 

fixed.  To communicate with PXM meter over TCP/IP 

DNP, the master must use 20,000 as port number.

5.2 Global Settings

When this page is selected, the User can configure the fol-

lowing parameters.

1.  DNP Select Operation Timeout
This parameter is used for Select-Before-Operate (SBO) 

operation on digital outputs (relays).  If the SBO mode is 

used by the master to operate meter’s digital outputs, then 

“DNP Select operation timeout” parameter is used.  In this 

particular operation, the DNP3 master first sends a select 

request for particular digital output.  When this request is 

received, the PXM meter starts a timer for duration speci-

fied by “DNP Select operation timeout” parameter.  If the 

operate command is received from DNP3 master before 

this timer elapses, then that digital output is operated as 

per the master request. 
If this timer expires before the operate request is received, 

then the operate request is rejected by PXM meter.

otee:

N

It is necessary that the digital I/O card is installed in 

the PXM meter to use this option.  SBO operation is 

supported only on relays R1, R2, and R3 and these 

relays should be selected in the DNP input output 

section as explained later in this document.

2.  DNP Default Object X Variation ( X =1, 2, 10, 20, 21, 22, 

23, 30, 32, 34, 40)
The DNP3 master may send requests to get the DNP3 

slave data (PXM data) objects with variation 0.  In this 

case, the meter can send responses with the default 

variation.  It is possible to configure object wise default 

variation for the PXM meter on web page.  The User 

can select the default variation from the drop down list 

given against each object.

Summary of Contents for PXM4K Series

Page 1: ...PXM 4 6 8K DNP3 Ethernet Communications User Manual PXM 4 6 8K DNP3...

Page 2: ...Event Data 6 2 4 Unsolicited Responses 7 2 5 Implementation Levels 7 2 6 Summary 7 3 DNP DEVICE PROFILE 8 4 IMPLEMENTATION TABLE 12 5 DNP3 ETHERNET COMMUNICATION SETUP CONFIGURATION UTILITY 16 5 1 DN...

Page 3: ...e the breakers and voltage regulators DNP3 uses the term outstation to denote remote comput ers as are found in the field The term master is used for the computers in the control centers DNP3 provides...

Page 4: ...ical analog quantities such as those used for set points Figure 1 Master and Outstation Relationship The elements of the arrays are labeled 0 through N 1 where N is the number of blocks shown for the...

Page 5: ...matching DNP3 User s code at the other end More will be said about data types and software lay ers later but first we want to examine a few typical system architectures where DNP3 is used Figure 2 Com...

Page 6: ...database where it is retrievable by a master station on the left side of the figure This design is often seen in substations where the data concentrator col lects information from local intelligent de...

Page 7: ...ame contains a pair of CRC octets for every 16 data octets This provides a high degree of assurance that communication errors can be detected The maximum number of octets in the data payload is 250 no...

Page 8: ...on numbers as fol lows 1 A 32 bit integer value with flag 2 A 16 bit integer value with flag 3 A 32 bit integer value 4 A 16 bit integer value 5 A 32 bit floating point value with flag and 6 A 64 bit...

Page 9: ...ly transmits a response without having received a specific request for the data Not all out stations have this capability This mode is useful when the system has many outstations and the master requir...

Page 10: ...ave Notable objects functions and or quali ers supported in addition to the Highest DNP Levels Supported For static non change event object requests request quali er codes 07 and 08 limited quantity a...

Page 11: ...messages Timeouts while waiting for Data Link Con rm None Fixed at ____ Variable Con gurable Complete Appl Fragment None Fixed at ____ Variable Con gurable Application Con rm None Fixed at 10 Sec Vari...

Page 12: ...e or the other Reports time tagged Binary Input Change Events when no speci c variation requested Never Binary Input Change With Time Binary Input Change With Relative Time Con gurable to Binary Input...

Page 13: ...Over at No Counters Reported Con gurable 16 Bits 32 Bits Other Value _____ Point by point list attached Sends Multi Fragment Responses Yes No Con gurable as Always or When reporting Event Data Sequen...

Page 14: ...ited qty 17 28 index 129 response 00 01 start stop 17 28 index see note 2 1 2 Binary Input with Status 1 read 00 01 start stop 06 no range or all 07 08 limited qty 17 28 index 129 response 00 01 start...

Page 15: ...l 07 08 limited qty 17 28 index 129 response 00 01 start stop 17 28 index see note 2 21 2 16 Bit Frozen Counter with Flag 1 read 00 01 start stop 06 no range or all 07 08 limited qty 17 28 index 129 r...

Page 16: ...p 06 no range or all 07 08 limited qty 17 28 index 129 response 00 01 start stop 17 28 index see note 2 30 3 default see note 1 32 Bit Analog Input without Flag 1 read 00 01 start stop 06 no range or...

Page 17: ...ut Status 1 read 00 01 start stop 06 no range or all 07 08 limited qty 17 28 index 129 response 00 01 start stop 17 28 index see note 2 40 3 Short floating point Analog Output Status 1 read 00 01 star...

Page 18: ...asy to use web based interface is provided to configure DNP parameters and database as per user requirement Installer can get connected to meter by enter ing IP address of meter in a web browser No se...

Page 19: ...2017 www eaton com 5 1 DNP3 Node Identification Figure 6 DNP3 Node Identification Page If the User wishes to change parameters then the User first needs to press Edit option and Authenticate self to...

Page 20: ...0 as port number 5 2 Global Settings When this page is selected the User can configure the fol lowing parameters 1 DNP Select Operation Timeout This parameter is used for Select Before Operate SBO ope...

Page 21: ...Ethernet Communications User Manual MN150005EN January 2017 www eaton com Figure 8 DNP3 Global Settings Setup Edit Page 5 3 Communication The User can set the DNP3 stack communication related paramete...

Page 22: ...application layer frame sent by the PXM meter 2 Application Layer Multiple Fragment Responses Allowed This parameter indicates weather the PXM meter is allowed to send multiple application fragments...

Page 23: ...the PXM meter shall expect a data link confirmation from the DNP master If the data link frame contains static information then the PXM meter shall not expect a data link con firmation from the DNP m...

Page 24: ...There will be no time synchronization between the DNP master and PXM meter The PXM meter shall never set the time sync flag in IIN bytes Figure 11 Time Synchronization Type Page Interval The PXM mete...

Page 25: ...f PXM meter parameters vari ables which can be added to the PXM DNP slave database Using the DNP Input Output web page the User can select and configure the required meter parameters for the spe cific...

Page 26: ...ssword these buttons will not be operational The User needs to press the Edit button and enter credentials to access these options 1 Load Config The User can load a pre configured DNP database configu...

Page 27: ...to Meter option the newly configured database will not be effective After using this option the web interface will prompt the User if the PXM meter needs to be rebooted or not The User may choose to...

Page 28: ...selection list are deleted 3 Delete Deletes selected parameters in the selection list on particular a tab For example if the Delete button is pressed on Binary Counter tab then a particular select ed...

Page 29: ...27 5 DNP3 Ethernet Communication Setup Configuration Utility PXM 4 6 8K DNP3 Ethernet Communications User Manual MN150005EN January 2017 www eaton com Figure 18 Delete Button...

Page 30: ...Amps or greater than 510 Amps When this particular event is triggered the value of IA which caused the event becomes reference for next event comparison For binary counters if the difference delta be...

Page 31: ...nalog Input 32 Bit 18 VCN Volts Analog Input 32 Bit 19 VLNavg Volts Analog Input 32 Bit 20 VNG Volts Analog Input 32 Bit 21 Real Power Watts Watts Analog Input 32 Bit 22 Reactive Power VAr VAr Analog...

Page 32: ...Bit 57 Reverse Wh kWh Counter 32 Bit 58 Reverse Wh Roll Over Counter kWh Counter 16 Bit 59 Sum Total Wh kWh Counter 32 Bit 60 Sum Total Wh Roll Over Counter kWh Counter 16 Bit 61 Delivered Leading VAr...

Page 33: ...r kWh Counter 16 Bit 101 Real Reverse Energy Rate A kWh Counter 32 Bit 102 Real Reverse Energy Rate A Roll Over Counter kWh Counter 16 Bit 103 Real Reverse Energy RTP kWh Counter 32 Bit 104 Real Rever...

Page 34: ...nergy RTP kvarh Counter 32 Bit 140 Reactive Net Energy RTP Roll Over Counter kvarh Counter 16 Bit 141 Total Reactive Net Energy kvarh Counter 32 Bit 142 Total Reactive Net Energy Roll Over Counter kva...

Page 35: ...it 183 Even Harmonic Distortion Magnitude Phase C Current Amps Analog Input 32 Bit 184 Even Harmonic Distortion Magnitude VCA Volts Analog Input 32 Bit 185 Even Harmonic Distortion Magnitude VCN Volts...

Page 36: ...nitude Phase B Current Amps Analog Input 32 Bit 220 Total Harmonic Distortion Magnitude VBC Volts Analog Input 32 Bit 221 Total Harmonic Distortion Magnitude VBN Volts Analog Input 32 Bit 222 Total Ha...

Page 37: ...log Input 32 Bit 266 Voltage Phasor VCN Quadrature Volts Analog Input 32 Bit 267 Voltage Phasor VAB Direct Volts Analog Input 32 Bit 268 Voltage Phasor VAB Quadrature Volts Analog Input 32 Bit 269 Vol...

Page 38: ...active Demand Power Peak Dmd Rate RTP var Analog Input 32 Bit 305 Last Month Net Reactive Demand Power Peak Dmd Rate A var Analog Input 32 Bit 306 Last Month Net Reactive Demand Power Peak Dmd Rate RT...

Page 39: ...nd Current Peak Dmd Rate A Amps Analog Input 32 Bit 348 Last Reset Demand Current Peak Dmd Rate RTP Amps Analog Input 32 Bit 349 Last Reset Fwd Real Demand Power Peak Dmd Rate A Watts Analog Input 32...

Page 40: ...386 Last Reset Net Reactive Demand Power Peak Dmd Rate RTP var Analog Input 32 Bit 387 Last Reset Net Reactive Power Accum Rate A kvarh Counter 32 Bit 388 Last Reset Net Reactive Power Accum Rate A R...

Page 41: ...Month Demand Q Fwd Rate A Peak Vars Analog Input 32 Bit 426 Current Month Demand Q Fwd Rate RTP Peak Vars Analog Input 32 Bit 427 Current Month Demand Q Net Rate A Peak Vars Analog Input 32 Bit 428 Cu...

Page 42: ...Form C Relay 2 Status 0 Digital Output 16 Bit 458 Form C Relay 3 Status 0 Digital Output 16 Bit 459 Discrete Input 1 Count 0 Counter 16 Bit 460 Discrete Input 2 Count 0 Counter 16 Bit 461 Discrete Inp...

Page 43: ...41 Appendix A Points List PXM 4 6 8K DNP3 Ethernet Communications User Manual MN150005EN January 2017 www eaton com Notes...

Page 44: ...such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTI...

Reviews: