3
Technical Data
TD150029EN
Effective June 2019
PXM4/6/8K meter color touchscreen
display quick start guide
EATON www.eaton.com
For best results, use the default communication settings for the
PXM4/6/8K meter and PXM4/6/8K meter color touchscreen display
(115.2 kbps, 1 start bit, 1 stop bit, no parity).
otee:
N
By default, the PXM4/6/8K meter color touchscreen display is pre-
set for a PXM4/6/8K meter slave address of “01”. To accommodate a dif-
ferent slave address, the user MUST change the PXM4/6/8K meter color
touchscreen display’s “Modbus ID”. This number MUST match the rotary
switch located on the side of the meter. This setting can be found under
Settings > Meter ID.
Figure 7. Changing the Modbus ID.
Meter firmware requirements
•
The minimum meter firmware version required for compatibility is
13.3.6.1.
Technical information
•
640 x 480 pixel backlit VGA touch screen display.
•
Power: 24 Vdc input.
•
Recommended: PXM display power cable (67A2180H11)
between the display and PXM4/6/8K’s CM3 source
•
Optonal: PSG60E (85-264Vac), PSG60F (320-576Vac)
Display measurements
•
Height: 5.24 in. (133 mm);
•
Width: 6.81 in. (173 mm);
•
Depth: 1.54 in. (39 mm);
•
Weight: 1.32 lb (600 g);
•
Cutout dimensions: 4.61 in. x 6.18 in.(117.0 x 157.0 mm).
Ratings
•
Front bezel IP rating: IP65;
•
Operating temperature: 0 ~ 50°C (32 ~ 122°F);
•
Storage temperature: -20 ~ 60°C (-4 ~ 140°F);
•
Ambient humidity: 10% ~ 90% RH (0 ~ 40°C [32 ~ 104°F]),
10% ~ 55% RH (41 ~ 50°C [105.8 ~ 122°F]).