background image

3

Technical Data 

TD150029EN

Effective June 2019

PXM4/6/8K meter color touchscreen

display quick start guide

EATON www.eaton.com

For best results, use the default communication settings for the  

PXM4/6/8K meter and PXM4/6/8K meter color touchscreen display 

(115.2 kbps, 1 start bit, 1 stop bit, no parity).

otee:

N

By default, the PXM4/6/8K meter color touchscreen display is pre-

set for a PXM4/6/8K meter slave address of “01”.  To accommodate a dif-

ferent slave address, the user MUST change the PXM4/6/8K meter color 

touchscreen display’s “Modbus ID”.  This number MUST match the rotary 

switch located on the side of the meter. This setting can be found under 

Settings > Meter ID.

Figure 7. Changing the Modbus ID.

Meter firmware requirements

• 

The minimum meter firmware version required for compatibility is 

13.3.6.1. 

Technical information

• 

640 x 480 pixel backlit VGA touch screen display.

• 

Power: 24 Vdc input.

• 

Recommended: PXM display power cable (67A2180H11) 

between the display and PXM4/6/8K’s CM3 source

• 

Optonal: PSG60E (85-264Vac), PSG60F (320-576Vac)

Display measurements

• 

Height: 5.24 in. (133 mm);

• 

Width: 6.81 in. (173 mm);

• 

Depth: 1.54 in. (39 mm);

• 

Weight: 1.32 lb (600 g);

• 

Cutout dimensions: 4.61 in. x 6.18 in.(117.0 x 157.0 mm).

Ratings

• 

Front bezel IP rating: IP65;

• 

Operating temperature: 0 ~ 50°C (32 ~ 122°F);

• 

Storage temperature: -20 ~ 60°C (-4 ~ 140°F);

• 

Ambient humidity: 10% ~ 90% RH (0 ~ 40°C [32 ~ 104°F]),  

10% ~ 55% RH (41 ~ 50°C [105.8 ~ 122°F]).

Summary of Contents for PXM468K-DISP-6-XV

Page 1: ...June 2019 Technical Data TD150029EN PXM4 6 8K meter color touchscreen display quick start guide Figure 3 Cut out dimensions 4 Ensure proper gasket placement on the PXM4 6 8K meter color touchscreen display 5 Insert the PXM4 6 8K meter color touchscreen display through the cutout 6 Fit the supplied threaded pins in the retaining brackets The tips of the threaded pins must point towards the wider en...

Page 2: ... 2 PIN 3 RED WHITE BLACK BARE PIN 1 PHOENIX CONN TERMINATION PIN 3 PIN 5 PIN 7 RED BLACK WHITE DB9 SHELL DB9 TERMINATION H11 XV SHIELD WIRE TERMINATED to CM3 CM4 67A2181H02 67A2180H11 Included with the PXM4 6 8K meter color touchscreen display is a data cable to connect the DB9 of the color touchscreen display to 3 terminal COM 1 RS485 of the PXM4 6 8K meter The supplied cables are designed to con...

Page 3: ...ocated on the side of the meter This setting can be found under Settings Meter ID Figure 7 Changing the Modbus ID Meter firmware requirements The minimum meter firmware version required for compatibility is 13 3 6 1 Technical information 640 x 480 pixel backlit VGA touch screen display Power 24 Vdc input Recommended PXM display power cable 67A2180H11 between the display and PXM4 6 8K s CM3 source ...

Page 4: ... tractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODI...

Reviews: